Brochure
L Series (Page 39-42)
NOTES:
1. Table 1 based on up to 4-foot grille length. For longer lengths, correct
throw and NC per Table 2.
2. When using continuous grille lengths with alternate active and inactive
sections, a reduction in throw can be obtained by omitting the factors
contained in Table 2.
3. Bar style 30 and 0
Increase Table 1 NC + 5 NC
4. Supply air temperature effect on horizontal throw is shown in Table 3. verti-
cal down-throw at varying supply temperatures is shown in Table 4.
5. When spreading the air path with a horizontal deflection of 22º per side in
grille lengths up to 4 feet:
Multiply Table 1 Throw x .75
Increase Table 1 NC + 5 NC
Multiply Table 1 P
s
x 1.20
Multiply Table 5 A
k
x .90
6. Terminal velocities (V
t
) at the minimum and maximum throw (T) values
are rated at 125 FPM and 75 FPM respectively with corresponding room
velocities (V
r
) of 50 FPM and 35 FPM.
Sidewall Sill/Floor
00 and 15 30 and 01 00 and 15 30 and 01 Min.-Max. Min.-Max. @ -18F T @ -25F T
20 1½ .01 .01 500 575 6-9 1-2 8 9 <20
1½ .03 .04 750 865 7-10 2-3 25
2 .01 .01 475 545 6-9 1-2 20
1½ .05 .07 1000 1150 9-13 3-5 30
2 .02 .03 635 730 8-11 2-4 25
2½ .01 .01 460 530 7-10 2-3 20
1½ .03 .12 1250 1440 11-16 4-9 30
2 .03 .04 790 910 10-14 3-7 25
2½ .02 .03 575 660 9-13 2-6 20
3 <.01 .01 440 505 8-12 2-5 <20
2 .05 .07 950 1090 12-18 5-11 30
2½ .02 .03 690 795 11-16 4-9 25
3 .01 .01 530 610 10-14 3-7 20
4 <.01 .01 370 425 8-12 2-5 <20
2 .06 .08 111 0 1275 14-20 7-13 30
2½ .03 .04 810 935 13-19 6-12 30
3 .02 .03 660 760 11-16 4-9 25
4 <.01 .01 435 500 10-14 3-7 <20
2 .08 .10 1275 1450 16-23 9-16 30
2½ .04 .05 920 1060 15-21 8-14 30
3 .03 .04 700 805 13-18 6-11 25
4 .01 .01 495 570 11-16 4-9 20
2½ .05 .07 1030 1185 17-24 10-17 30
3 .04 .05 785 905 15-21 8-14 30
4 .01 .02 550 635 13-18 6-11 25
5 <.01 .01 450 520 11-16 4-9 20
2½ .06 .08 1150 1325 19-27 12-20 30
3 .04 .05 875 1010 16-23 9-16 30
4 .02 .03 620 715 14-20 7-13 25
5 .01 .01 500 575 12-18 5-11 20
3 .06 .08 1050 1210 19-28 11-20 30
4 .03 .04 745 855 17-24 9-16 30
5 .02 .03 600 680 15-22 7-14 25
6 <.01 .01 480 550 13-19 5-11 20
3 .08 .11 1220 1410 22-32 14-24 35
4 .04 .05 870 1000 19-28 11-20 30
5 .02 .03 700 810 17-25 9-17 25
6 .01 .01 560 645 15-22 7-14 20
4 .05 .07 990 1140 22-32 13-23 35
5 .03 .04 800 925 19-29 10-20 30
6 .02 .03 640 735 18-26 9-17 25
8 .01 .01 460 530 15-22 6-13 20
4 .07 .09 111 0 1275 25-36 16-27 35
5 .04 .05 900 1035 22-33 13-24 30
6 .03 .04 725 835 20-30 11-21 25
8 .02 .03 520 600 17-25 8-16 20
4 .08 .11 1240 1425 28-41 - 40
5 .05 .07 1000 1150 24-36 - 35
6 .04 .05 800 925 23-33 - 30
8 .02 .03 575 665 20-28 - 25
5 .08 .11 1250 1440 30-46 - 40
6 .05 .07 1000 1150 27-39 - 35
8 .03 .04 720 830 25-35 - 30
10 .01 .01 550 625 21-32 - 25
6 .07 .09 1200 1375 33-48 - 40
8 .04 .05 865 1000 29-42 - 35
10 .02 .03 665 765 25-39 - 30
12 .01 .01 545 630 23-33 - 25
8 .05 .08 1020 1175 34-48 - 40
10 .03 .04 780 900 29-45 - 35
12 .02 .03 640 735 26-38 - 30
8 .08 .11 1170 1350 40-55 - 45
10 .04 .05 890 1025 33-50 - 40
12 .03 .04 730 845 33-44 - 35
50
40
30
Throw (T) in Feet
Minimum Ceiling
Height in Feet
9 11
Table 1 - Supply Air
Min. P
s
in H
2
0
Bar Style
CFM/Ft of
total
Linear
length
Listed
Width
in
Inches
NC
9 10
60 9½ 12
9½ 11
Face Velocity (V
k
) FPM
Bar Style
70 10 12
80 10½ 12½
90 11 13
100 11 13
120 11½ 13
140 11½ 14
160 12 15
180 12 15
200 12 15
250 13 15
400 14 16
300 13 15
350 13 15
Symbols:
V
t
Terminal Velocity in FPM
V
r
Room Velocity in FPM
V
k
Face Velocity in FPM
A
k
Outlet Area in Square Feet
A
n
Neck Area in Square Feet
P
s
Static Pressure in H2O
NC 18dB Room Attenuation
T Throw in Feet: see Note 6.
∆T Temperature Differential
Recommended Noise Criteria and Face Velocity Ranges are on page 75114
Engineering Data
Engineering Data