Install Instructions
Type B Gas Vent - 3” to 12” Diameter
Installation Instructions
1
Please read and understand the requirements before proceeding.
Hart & Cooley Type B gas vent pipe and fittings are
Underwriters Laboratories-tested and listed to
Standard 441 for use with listed gas-fired appliances
that have been certified for use with Type B gas
vent. B-Vent is intended for neutral or negative draft
applications. It is designed for vertical installations
(including laterals) but may be used for horizontal
applications with a draft-inducing fan located such
that all indoor portions of the vent are under negative
pressure.
The materials in this B-Vent have been selected to
provide maximum resistance to corrosion and heat;
however, their use with temperatures exceeding
550° F or in highly corrosive atmospheres, such as
chlorinated hydrocarbons (i.e., refrigerants, dry-
cleaning fluids, degreasers, paint removers, etc.),
may substantially reduce their life expectancy.
These installation instructions will enable the in-
staller to make a safe and proper installation of the
vent. Compliance with these instructions will ensure
an installation that mee ts the requirements of all
National Building Codes and the National Fuel Gas
Code, NFPA 54 and NFPA 211. Hart & Cooley Type
B gas vents are listed under the follow-up service
of Underwriters Laboratories, Inc.
CAUTION
Flue gas temperatures must never exceed
550° F in any Hart & Cooley gas vent system.
Gas appliances that may be connected to Type
B gas vents
Type B gas vents may be used to vent gas
appliances listed for use with Type B gas vent.
These vents shall be installed in accordance with
our listing as detailed in these installation
instructions. The type of appliances that may be
vented with these vents include:
Unit heaters Room (space) heaters
Duct furnaces Central warm-air furnaces
Attic furnaces Hot-water boilers
Floor furnaces Steam boilers
Water heaters
CAUTION
Hart & Cooley Type B vents are not to be used
with appliances burning solid or liquid fuels.
Gas appliances that must be connected to
chimneys
The following appliances must be connected to
chimneys.
• All incinerators in domestic applications
• All appliances that may be converted readily t o
the use of solid or liquid fuels
• Combination gas/oil-burning appliances
• Unlisted appliances
General instructions
• The vent should always be sized for the sea-level
name plate input rating of appliances in
accordance with the procedures set forth in the
Gas Vent Capacity Tables, which appear in the
Gas vent chimney sizing & application guide
or in NFPA 54.
• Provide for adequate air supply for combustion
air and draft-hood dilution air. Refer to NFPA 54
or the application guide for recommended
arrangements and proper size of air supply
openings.
• Use only parts and fittings listed in the catalog to
ensure an approved vent.
Installation Instructions
Type B Gas Vent - 3" to 12" Diameter










