Install Instructions

Please read and understand the requirements before proceeding.
Hart & Cooley Type B gas vent pipe and fittings are
Underwriters Laboratories-tested and listed to
Standard 441 for use with listed gas-fired appliances
that have been certified for use with Type B gas vent.
B-Vent is intended for neutral or negative draft
applications. It is designed for vertical installations
(including laterals) but may be used for horizontal
applications with a draft-inducing fan located such
that all indoor portions of the vent are under negative
pressure.
The materials in this B-Vent have been selected to
provide maximum resistance to corrosion and heat;
however, their use with temperatures exceeding
550° F or in highly corrosive atmospheres, such as
chlorinated hydrocarbons (i.e., refrigerants, dry-
cleaning fluids, degreasers, paint removers, etc.),
may substantially reduce their life expectancy.
These installation instructions will enable the installer
to make a safe and proper installation of the vent.
Compliance with these instructions will ensure an
installation that meets the requirements of all National
Building Codes and the National Fuel Gas Code,
NFPA 54 and NFPA 211. Hart & Cooley Type B gas
vents are listed under the follow-up service of
Underwriters Laboratories, Inc.
Gas appliances that may be connected to Type B
gas vents
Type B gas vents may be used to vent gas appliances
listed for use with Type B gas vent.
These vents shall be installed in accordance with our
listing as detailed in these installation instructions.
The type of appliances that may be vented with these
vents include:
Unit heaters Room (space) heaters
Duct furnaces Central warm-air furnaces
Attic furnaces Hot-water boilers
Floor furnaces Steam boilers
Water heaters
Gas appliances that must be connected to
chimneys
The following appliances must be connected to
chimneys.
All incinerators in domestic applications
All appliances that may be converted readily to the
use of solid or liquid fuels
Combination gas/oil-burning appliances
Unlisted appliances
General instructions
The vent should always be sized for the sea-level
name plate input rating of appliances in accordance
with the procedures set forth in the Gas Vent
Capacity Tables, which appear in the Gas vent
chimney sizing and application guide or in NFPA
54.
Provide for adequate air supply for combustion air
and draft-hood dilution air. Refer to NFPA 54 or the
application guide for recommended arrangements
and proper size of air supply openings.
Use only parts and fittings listed in the catalog to
ensure an approved vent.
CAUTION
Flue gas temperatures must never exceed
550° F in any Hart & Cooley gas vent system.
CAUTION
Hart & Cooley Type B vents are not to be used
with appliances burning solid or liquid fuels.
Installation Instructions
Type B Gas Vent - 3" to 12" Diameter