reset will return the panel to its normal operating condition. To perform the fast reset, press the RESET
button. The panel completes a fast reset in approximately 5-10 seconds.
Forced reset
The forced reset is similar to the fast reset, except that non-resettable events are forced to reset. To force
a reset, press and hold the RESET button until the panel starts to reset (approx. 5 seconds). After the
panel has restarted, it is likely that some events will reactivate because the condition that caused them is
still present. The panel completes a forced reset in approximately 5-10 seconds.
Full reset
The full reset powers down all circuits, even non-resettable circuits, during the reset. All modules perform
their startup initialization. To perform a full reset, press PROG to enter the passcode screen, then press
RESET. If you are in programming mode and press RESET, this is the type of reset that occurs. The panel
completes a full reset in approximately 20-30 seconds, with SLCs completing their startup 10-20 seconds
after that.
Table 2-1: Annunciator Buttons
Button
Action (normal mode*)
C D
Browse forward or backward through alarm event list
A B
Browse forward or backward through the non-alarm event list
ACK
NOWLEDGE
Turn off the annunciator’s buzzer
SILENCE
Turn off building notification and other outputs activated by off-normal events. The SILENCE LED
flashes when this button is activated.
RESET
Reset devices that are in alarm to a normal condition. See 2.4.1 for details.
Fast Reset: press RESET
Forced Reset: press and hold RESET
Full Reset: press PROG, then press RESET.
Alphanumeric keypad
(other than 0)
Used for programming only.
PROG
Enter the menu system.
* Refer to the programming sections of this manual and the programming manual for the programming mode functions of
the buttons.