CCWI 181 Install info
Color ......................................White
Consistency ...........................Heavy textured
Base .......................................Synthetic latex
Solvent ..................................Water
Weight per Gallon ................11.6 lbs. (+/- 0.2)
Solids Content ......................70% (+/- 2)
Viscosity ................................Thixotropic
Coverage (UL 181 A-M) ........... Apply 18 mil, scrim and 18 mil
over scrim.
(UL 181 B-M) ............................... Approximately 214 to 320 lin.
ft. per gal. at 30 to 35 mil wet
film thickness at 3" width.
Shore A Hardness .................>20
Flexibility ..............................Passes
1
/
4
inch mandrel bend
Time to Test .......................... 48 hours*
Service Temperature ........... -20°F to 200°F
Mildew Resistance ............... Mold & Mildew resistant
VOC .......................................45 g/l (less water)
Pressure Classes ................... SMACNA
1
/
2
, 1, 2, 3, 4, 6 and
10 inches w.g.
Seal Classes ......................... SMACNA A, B, C
Packaging ............................. 1, 2 & 5 gal. pails; 10.3 oz. cart.
Freeze/Thaw Stability .........Passed 5 Cycles
Specification Compliance ...Passes ASTM C-731, ASTM
D-2202. USDA, EPA and FDA
Approved
A versatile, all purpose duct sealant for use on all types of metal duct, glass fiber
duct board, and flex duct, as well as duct fabric and flexible tubing runouts. CCWI
181 incorporates a built-in polyester reinforcement for exceptional strength,
with UV inhibitors for outdoor use. UL 181A-M listed / UL 181B-M listed.
z INDOOR/OUTDOOR
z POLY REINFORCEMENT
z NO-SAG FORMULATION
z PROVEN RELIABILITY
PRECAUTIONSPRECAUTIONS
PRECAUTIONSPRECAUTIONS
PRECAUTIONS
Surface must be clean and free of moisture, contamination and
foreign matter. Do not allow this product to freeze. Do not apply
when rain or freezing temperatures will occur within 36 hours. Do
not apply this product where temperatures will exceed 200
O
F.
Keep out of the reach of children. Review MSDS for complete
safety information prior to use. DO NOT use where acidic or
alkaline chemicals are present (ie., lab fume hood, vents, etc.)
For Industrial Professional Use Only.
Printed in U.S.A 012/03 ©The Carlisle Corporation
TECHNICAL DATA
Underwriters Laboratories Inc.
®
LISTED
17NF
UL 181A-M
®
FOR USE WITH U.L. LISTED RIGID
FIBERGLASS AIR DUCTS OR CONNECTORS.
UL 181B-M
FOR USE WITH U.L. LISTED FLEXIBLE
AIR DUCTS OR CONNECTORS.
CCWI-181
Indoor/Outdoor Water Based Duct Sealant
CCWI-181
For additional information contact:
Carlisle Coatings & Waterproofing
Incorporated
900 Hensley Lane
Wylie, Texas 75098
Phone: (800) 527-7092 FAX: (972) 442-0076
WWW.HARDCAST.COM
City of Los Angeles Approval RR#8069
*May vary according to
temperature and humidity
APPLICATION
Temperature .................. 35°F to 110°F (1.7°C to 44°C)
Method ........................... Brush, putty knife, caulk gun,
pump
Preparation .................... Surface must be dry, dirt, oil,
and grease free.
Rate (UL 181 A-M): ......... Apply 18 mil, scrim and 18 mil
over scrim.
(UL 181 B-M): .................. Approx. 214 to 320 lin. ft. per
gal. at 30 to 35 mil wet film
thickness at 3" width.
Clean Up Wet ................. Soap and water
Clean Up Dry .................. UNN-GRIP
™
798-ES or Solvent
(Use safe handling practices.)
Painting .......................... Only latex or epoxy paints
Ductboard .......................
Scrim required for UL 181A-M
STORAGE
DO NOT FREEZE
Temperature .................. 35°F to 110°F (1.7°C to 44°C)
Shelf Life ........................
One year (unopened)
Flammability .................. Non-flammable
Apply to entire surface of duct joint