User Guide

9
8
FRONT PANEL
Left panel
1. LCD display
2. Fine and Coarse trimmers to precisely set the lower level
3. Fine and Coarse trimmers to precisely set the higher level
4. Offset and Slope calibration trimmers
5. Selects actual measurement (MEASURE) or setpoint (SET) to
be displayed on the LCD
6. Selects "LO" and "HI" setting modes
7. Graded dial for manual temperature compensation
Right panel
8. Triple contact alarm to select the alarm in a normally-closed
(NC) or a normally open (NO) position. The alarm contact is
activated when the pH varies by more than -2.0 pH from
“SET LO” and +2.0 from “SET HI” setpoint values.
9. Control contacts:
Three terminals marked "Temperature Compensation Select"
to select automatic or manual temperature compensation
mode
Three terminals marked "Out mA Select" to select between
0 to 20 mA or 4 to 20 mA isolated output.
Specifications WM 8910D WM 8910U
RANGE 0.00 to 14.00 pH
RESOLUTION 0.01 pH
ACCURACY ±0.02 pH
(@20°C/68°F)
TYPICAL EMC ±0.1pH
DEVIATION
mA OUTPUT User selectable 0 to 20 mA or 4 to 20 mA
in a 0-14 pH range with isolated output
OFFSET Through "OFFSET" trimmer
CALIBRATION (Max. ±1.5 pH regulation)
SLOPE Through "SLOPE" trimmer
CALIBRATION from 80% to 110%
TEMPERATURE Manual or automatic
COMPENSATION from -10 to 80°C (14 to 176°F)
SETPOINT From 0.00 to 14.00 pH with 2 trimmers: "COARSE" for
RANGE an approximate regulation and "FINE" for fine tuning.
In addition, setpoint controls are activated through the
"CONTROL SELECT" terminals: "ACID"
or "BASE" for acid or basic dosage.
ALARM Through a relay which provides a normally open or a
CONTACT normally closed contact output (isolated output Max.
2A, Max. 240V, resistive load, 1,000,000 strokes).
The alarm contact will be activated if the pH
varies by more than ±2 pH from setpoint.
POWER SUPPLY 220/240V 110/115V
50/60Hz 50/60Hz
POWER SUPPLY One plug for the pH dosage (115 or 220V, depending
FOR DOSING on the model, Max.2A, 1,000,000 strokes)
ENVIRONMENT -10 to 50°C (14 to 122°F)
max. 85% RH non-condensing
PROTECTION IP54
WEIGHT 1.6 Kg (3.5 lb.)
ENCLOSURE 181 x 221 x 142mm (7.1 x 8.7 x 5.6")
MATERIAL Housed in rugged, fiber-reinforced polypropylene case
FUNCTIONAL DESCRIPTION WM 8911FUNCTIONAL DESCRIPTION WM 8911
FUNCTIONAL DESCRIPTION WM 8911FUNCTIONAL DESCRIPTION WM 8911
FUNCTIONAL DESCRIPTION WM 8911
DUAL SETPOINT, DUAL SETPOINT,
DUAL SETPOINT, DUAL SETPOINT,
DUAL SETPOINT,
pHpH
pHpH
pH
CONTROLLER CONTROLLER
CONTROLLER CONTROLLER
CONTROLLER