User Guide

34
If asking for last calibration data and the controller was never
calibrated, it answers with “0”; e.g. “01<STX>0<ETX>”.
If the controller was calibrated, it answers with “1” followed
by the calibration data. The Data field of the answer has the
following format:
pH 502:
1<Date><Time><Offset><Slope1><Slope2><Buf1><Buf2><Buf3>
Date: DDMMYY (e.g. “170400” for April 17,2000)
Time: HHMM (e.g. “1623” for 4:23 pm)
Offset: ASCII string (e.g. “
-
0.2”)
Slope 1: ASCII string (e.g. “62.5”)
Slope 2: ASCII string (e.g. “60.4”)
Buf 1: ASCII string (e.g. “7.01”)
Buf 2: ASCII string (e.g. “4.01”)
Buf 3: ASCII string (e.g. “10.01”)
mV 602: 1<Date><Time><Buf1><Buf2>
Date: DDMMYY (e.g. “170400” for April 17,2000)
Time: HHMM (e.g. “1623” for 4:23 pm)
Buf 1: ASCII string (e.g. “7.01”)
Buf 2: ASCII string (e.g. “4.01”)
The items in the Data field are separated by blanks.
If an item is not available (e.g. Buf 3 if only a two points
calibration was performed) it is replaced by the “N” charac-
ter.
Note The “r485” message can appear on the LCD while the con-
troller is receiving or answering commands.
SETTING THE BAUD RATE
The transmission speed (baud rate) of the meter and external
device must be th same.
The meter is factory set to 9600 bps. To change this value,
use setup item 71.