Cut Sheet

Table Of Contents
Specification Sheet
Mini Power Center
HPS PowerPlus™
15 year on transformer, 1 year on mini power center
Single Phase
Aluminum
Ratings include: 5, 7.5, 10, 15, 25 kVA
All welded core construction made with high quality, high permeability silicon steel laminations
Aluminum winding
Front accessible wiring compartment with high and low voltage lead wires or copper tabs.
Standard: wall mounting.
60 Hertz
Warranty
Phase
Winding Material
Rating
Voltage 480 Primary, 120/240 Secondary
Core
Coil
Termination
Heavy Duty Ventilated Type 3R in ANSI 61 Grey painted finish with knock outs for indoor and
outdoor applications. Encapsulated with electrical grade silica sand and resin compounds.
Enclosure
Mounting
Frequency
180° insulation classInsulation System
UL listed (cULus marked and approved for both the US and Canada)
Approvals and Standards
Shielded transformer
Combines a pre-wired primary and secondary main
breaker, secondary power panel and dry-type
shielded transformer
Features and Benefits
Primary taps: 2 - 5% FCBN
Stainless Steel Enclosures
Options
PL32- Page 1 of 1SS_sPowPlu
Data subject to change without notice. Please visit www.hammondpowersolutions.com for the most current data.
Printed: December 18, 2014