6. Enter the desired WATER FLOW
calibration factor by pressing the
INCREASE or DECREASE buttons
( or ) to change the value of the
flashing digit. (See Figure 4.)
Press the red ON/OFF button ( ) to
select the next digit it begins flashing.
(See Figure 4a.)
7. Press and hold the DISPLAY button
(
i) until PASS is shown. (See Figure 1
on preceding page.)
8. With the DISPLAY button (
i) pressed,
press the DECREASE and INCREASE
buttons in this order: DECREASE,
INCREASE, DECREASE, INCREASE
( ). (See Figure 5 in the next
column.)
The right-most decimal flashes with
each INCREASE and DECREASE
button press.
9. Release the DISPLAY button (
i).
The display shows ScAL and resumes
normal operation. (See Figure 6.)
10. Direct water and foam calibration is
now complete.
DD
DD
D
DD
DD
D
DD
DD
D
DD
DD
D
Manual p/n: 113965 Rev -, 04/11/2006