User Manual

57
CAFS Bottled-Air Operator/s Guide
p/n: 029-0020-85-0
Routine Maintenance
6 Routine maintenance
6.1 MAINTENANCE PROCEDURES
After each use
Inspect wiring, hoses, flow sensors and connections for tightness, cor-
rosion, leaks and/or damage. (See Section 4, heading 4.7 “Plumbing,
on page 31.) Also see Section 4, heading “Electrical” on page 38.
Verify status of the CAFSAttack air filter element. See heading 6.2
“Replace Filter Element” on page 58.
Clean inspect the CAFSAttack system for after each use.
Verify status (charge) of the air-bottle cylinders. (See Section 2, head-
ing “Intelli-Tank Air Level Indicator, on page 22.). Refill as needed.
(See Section 2, heading “Air Bottle FILL Coupling,” on page 22.)
Flush the foam pump if a non-approved foam concentrate is used.
Also see “Appendix B: Foam Concentrate Compatibility” on page 61.
See your specific FoamLogix manual, provided with the system, for
additional maintenance procedures.
Monthly
See your specific FoamLogix manual, provided with the system, for
maintenance procedures.
Verify air flow calibration. (See Section 5 “Preset calibration,” on page
51.)
Visually and functionally inspect the CAFSAttack system for leaks and
proper system operation.
Ensure that all shut-off valves and switches function properly.
Every Two (2) Months
See your specific FoamLogix manual, provided with the system, for
maintenance procedures.