Instructions / Assembly

Mounting
1. Remove the lens by removing the screw securing it to the rear housing and set aside.
2. Remove screws and remove reector from rear housing.
Power From Conduit
1. Knock out two plugs in rear housing and apply the gasket to the back surface of housing. Attach xture to mounting
surface with two screws.
a. For surface conduit: Remove the threaded plug from the bottom of the rear housing.
b. For conduit entry from back: Knock out the conduit entrance on back of xture.
2. Complete the wiring to the power source and ground (refer to wiring instructions).
3. To ensure rain tight seal, apply silicone caulking around back edges of xture.
4. Replace reector.
5. Replace front lens by reversing procedure used to remove it.
Mounting Over Outlet Box
1. Knock out appropriate holes around outlet hole in rear housing and apply the gasket to the back surface of housing.
Fasten the rear housing to the outlet box using the screws supplied with the outlet box.
2. Complete the wiring to the power source and ground (refer to wiring instructions).
3. To ensure rain tight seal, apply silicone caulking around back edges of xture.
4. Replace reector.
5. Replace front lens by reversing procedure used to remove it.
Fixture Wiring
NOTE: This luminaire is rated for 120-277V 50/60Hz only.
1. Make the following electrical connections in the mounting box or junction box:
a. Connect the black xture lead to the voltage supply lead
b. Connect the white xture lead to the neutral supply lead
c. Connect the ground lead to the supply ground lead.
LED
Mini Wall Pack Series
Installation Instructions
®
© 2018 Halco Lighting Technologies, LLC. All rights reserved. Halco and ProLED are registered trademarks of Halco Lighting Technologies. All sizes and specications are subject to change. Print Edition 06-13-18
Halco Lighting Technologies | 2940 Pacic Drive | Norcross, GA 30071 | Toll Free 800.677.3334 | Phone 770.242.3612 | Fax 800.880.0822 | halcolighting.com | Atlanta | Cleveland | Houston | Los Angeles | Phoenix
Important:
This product is warranted for 5 years from the date of purchase, based on 10 hours of use per day. If this product does not
perform to the specications supplied on this package, send an email or write to the address below for product return and
replacement. This replacement is the sole remedy available. Liability for incidental or consequential damage is expressly
excluded. Visit www.halcolighting.com for full warranty details and compatibility information.
Warranty Information:
This product is warranted for 5 years from the date of purchase, based on 10 hours of use per day. If this product does not perform to the specications
supplied on this package, send an email or write to the address below for product return and replacement. This replacement is the sole remedy available.
Liability for incidental or consequential damage is expressly excluded. Visit www.halcolighting.com for full warranty details and compatibility information.
External cable
GND L N
Fixture Housing GRD
LED
WHITEN REDLED+V+
BLACKDLRIVER
GND BLACKLED
V
-
-
Driver Wiring Diagram:
REDLOAD
WHITEN
BLACKL
DRIVER
GND
N
L
L
Photocell Wiring Diagram:
External cable
N GND
Photocell