9000 BTU/HR COMPACT CASSETTE TYPE INDOOR INVERTER DRIVEN HEAT PUMP SYSTEM
1U09EH2VHE / AB09SC2VHA
Outdoor Unit
Compressor DC inverter Driven Rotary
Uncrated Dimension (HxWxD)
27 1/2 x 35 x 13 7/8 in
(697 x 890 x 353 mm)
Crated (HxWxD)
31 1/2 x 41 1/8 x 18 1/8 in
(800 x 1046 x 460 mm)
Outdoor Sound Rating dB 54
Heat Exchanger Fin Type Blue Fin
Weight (Ship/Net) 115.5/98.3 lbs
Factory Refrigerant Charge R-410A (56.8 oz)
Indoor Unit
Uncrated Dimension (HxWxD)
10 1/4 x 22 1/2 x 22 1/2 in
(260 x 570 x 570 mm)
Crated (HxWxD)
15 x 28 1/4 x 26 3/4 in
(380 x 718 x 680 mm)
Panel Uncrated Dimension
(HxWxD)
2 3/8 x 27 1/2 x 27 1/2 in
(60 x 700 x 700 mm)
Panel Crated (HxWxD)
4 1/2 x 29 1/8 x 29 1/8 in
(115 x 718 x 718 mm)
Airow CFM
(Turbo/High/Med/Low/Quiet)
410/365/305/265/205
Indoor Sound Level dB
(Turbo/High/Med/Low/Quiet)
43/40/37/34/31
Motor Rating (HP) 0.033
Heat Exchanger Fin Type Blue Fin
Condensate Pump Included - 27.5 in. Max Lift
Drain Pipe Size OD 1 1/4 in.
Weight (Ship/Net) 43.9/34 lbs
1U09/12EH2VHD
35 (890)
27 1/2 (697)
13 7/8 (353)
Floor Mounting
Dimensions
5 1/8
(130)
24 3/4
(629)
5 7/8
(149)
14
(356)
Heating Capacity Data
Outdoor
Air Temp
DB
Indoor Set Temperature
60
O
F (16
O
C) 70
O
F (21
O
C) 77
O
F (25
O
C)
Maximum
Capacity (Btu/h)
Power Usage
(w) COP
Maximum
Capacity (Btu/h)
Power Usage
(w) COP
Maximum
Capacity (Btu/h)
Power Usage
(w) COP
-31
O
F (-35
O
C) 2,100 691 0.89 2,000 727 0.81 1,960 734 0.78
-22
O
F (-30
O
C) 4,200 872 1.41 4,000 969 1.21 3,800 979 1.14
-15
O
F (-26
O
C) 5,250 1,026 1.5 5,000 1,140 1.29 4,750 1,163 1.2
-4
O
F (-20
O
C) 7,350 1,274 1.69 7,000 1,341 1.53 6,650 1,368 1.42
5
O
F (-15
O
C) 9,450 1,416 1.96 9,000 1,490 1.77 8,550 1,565 1.60
17
O
F (-8
O
C) 11,025 1,596 2.02 10,500 1,680 1.83 9,975 1,764 1.66
47
O
F (8
O
C) 12,075 1,226 2.89 11,500 1,290 2.61 10,925 1,355 2.36
Capacity and power usage are measured under the assumption of indoor humidity of 46%
* Cooling Capacity under low ambient temperature below 23
O
F (-5
O
C) are tested when using wind bae on outdoor unit
Cooling Capacity Data
Outdoor
Air Temp
DB
Indoor Set Temperature
70
O
F (21
O
C) 75
O
F (24
O
C) 80
O
F (27
O
C)
Maximum
Capacity (Btu/h)
Power Usage
(w) EER
Maximum
Capacity (Btu/h)
Power Usage
(w) EER
Maximum
Capacity (Btu/h)
Power Usage
(w) EER
14
O
F (-10
O
C)* 10,548 653 16.15 10,768 629 17.12 10,988 605 18.16
32
O
F (0
O
C) 10,528 661 15.93 10,748 636 16.90 10,967 612 17.92
50
O
F (10
O
C) 10,508 667 15.75 10,727 643 16.68 10,946 618 17.71
65
O
F (18
O
C) 10,487 674 15.56 10,706 649 16.50 10,924 624 17.51
75
O
F (24
O
C) 10,384 681 15.25 10,601 656 16.16 10,817 631 17.14
85
O
F (29
O
C) 10,282 688 14.94 10,496 662 15.85 10,710 637 16.81
95
O
F (35
O
C) 9,072 983 9.23 9,261 946 9.79 9,450 910 10.38
105
O
F (41
O
C) 8,800 993 8.86 8,984 956 9.40 9,167 919 9.97
115
O
F (46