Submittals

Next Gen Arctic Series Submittal
Rev. Feb 2021
12000 BTU/HR FLOOR CONSOLE INVERTER DRIVEN HEAT PUMP SYSTEM
1U12EH2VHE / USYF12UCDWA
Job Name: __________________________________
Purchaser: __________________________________
Submitted To: _______________________________
Construction: _______________________________
Reference: __________________________________
Approval: ___________________________________
Date: ______________________________________
Submitted By: _______________________________
Unit: _______________________________________
Drawing #: __________________________________
Electrical Requirement
Power Supply
208/230V, 1 Phase,
60 HZ
Operating Voltage Range 187~253 VAC
Recommended Fuse/Breaker Size 20A
MCA 14A
Cooling Performance
Rated Cooling Capacity 11,500 BTU
Cooling Capacity Range 3,100~13,600 BTU
Rated Power input 910 W
SEER 20.0
EER 12.5
Moisture Removal 3.2 Pt./h
Heating Performance
Rated Heating Capacity 12,500 BTU
Heating Capacity Range 3,100~21,000 BTU
Rated Power Input 1,480 W
HSPF 10.0
For more information visit us:
www.Haierductless.com
www.Haierductlesshelp.com
Connecting cable to indoor units must be 14/4 AWG unshielded stranded
copper. Cable must be ran continuous, without splicing.
Accessories
Pipe Length
Minimum Pipe Length 10 ft
Maximum Pipe Length 50 ft
Maximum Pipe Height Dierence 33 ft
Flare Connections
Liquid
Outdoor: 3/8”*
Indoor: 1/4”*
Vapor 1/2”
*use adaptor shipped with outdoor unit
Remote Controller
Ships with Standard Remote Control (WJ01X24721)
Wired Controller
Compatible with the Simplied (QACT17A) and
Programmable (YR-E16B) wall controllers.
Built-in WiFi
CUS
Intertek
Operating Range
Cooling With Wind Bae 14~115°F (-10~46°C)
Cooling Without Wind Bae 23~115°F (-5~46°C)
Heating -31~75°F (-35~24°C)