Submittals
Next Gen Arctic Series Submittal
Rev. Feb 2021
12000 BTU/HR COMPACT CASSETTE TYPE INDOOR INVERTER DRIVEN HEAT PUMP SYSTEM
1U12EH2VHE / AB12SC2VHA
Outdoor Unit
Compressor DC inverter Driven Rotary
Uncrated Dimension (HxWxD)
27 1/2 x 35 x 13 7/8 in
(697 x 890 x 353 mm)
Crated (HxWxD)
31 1/2 x 41 1/8 x 18 1/8 in
(800 x 1046 x 460 mm)
Outdoor Sound Rating dB 54
Heat Exchanger Fin Type Blue Fin
Weight (Ship/Net) 124.8/107.6 lbs
Factory Refrigerant Charge R-410A (62.1 oz)
Indoor Unit
Uncrated Dimension (HxWxD)
10 1/4 x 22 1/2 x 22 1/2 in
(260 x 570 x 570 mm)
Crated (HxWxD)
15 x 28 1/4 x 26 3/4 in
(380 x 718 x 680 mm)
Panel Uncrated Dimension
(HxWxD)
2 3/8 x 27 1/2 x 27 1/2 in
(60 x 700 x 700 mm)
Panel Crated (HxWxD)
4 1/2 x 29 1/8 x 29 1/8 in
(115 x 718 x 718 mm)
Airow CFM
(Turbo/High/Med/Low/Quiet)
410/365/305/265/205
Indoor Sound Level dB
(Turbo/High/Med/Low/Quiet)
45/42/39/36/33
Motor Rating (HP) 0.033
Heat Exchanger Fin Type Blue Fin
Condensate Pump Included - 27.5 in. Max Lift
Drain Pipe Size OD 1 1/4 in.
Weight (Ship/Net) 48.5/40.8 lbs
1U09/12EH2VHD
35 (890)
27 1/2 (697)
13 7/8 (353)
Floor Mounting
Dimensions
5 1/8
(130)
24 3/4
(629)
5 7/8
(149)
14
(356)
Heating Capacity Data
Outdoor
Air Temp
DB
Indoor Set Temperature
60
O
F (16
O
C) 70
O
F (21
O
C) 77
O
F (25
O
C)
Maximum
Capacity (Btu/h)
Power Usage
(w) COP
Maximum
Capacity (Btu/h)
Power Usage
(w) COP
Maximum
Capacity (Btu/h)
Power Usage
(w) COP
-31
O
F (-35
O
C) 3,150 893 1.03 3,000 940 0.94 2,850 987 0.85
-22
O
F (-30
O
C) 5,250 1,190 1.29 5,000 1,253 1.17 4,750 1,316 1.06
-15
O
F (-26
O
C) 7,350 1,400 1.54 7,000 1,474 1.39 6,650 1,548 1.26
-4
O
F (-20
O
C) 9,450 1,556 1.78 9,000 1,638 1.61 8,550 1,720 1.46
5
O
F (-15
O
C) 11,550 1,729 1.96 11,000 1,820 1.77 10,450 1,911 1.60
17
O
F (-8
O
C) 12,941 1,682 2.25 12,325 1,770 2.04 11,709 1,859 1.85
47
O
F (8
O
C) 15,015 1,577 2.79 14,300 1,660 2.52 13,585 1,743 2.28
Capacity and power usage are measured under the assumption of indoor humidity of 46%
* Cooling Capacity under low ambient temperature below 23
O
F (-5
O
C) are tested when using wind bae on outdoor unit
Cooling Capacity Data
Outdoor
Air Temp
DB
Indoor Set Temperature
70
O
F (21
O
C) 75
O
F (24
O
C) 80
O
F (27
O
C)
Maximum
Capacity (Btu/h)
Power Usage
(w) EER
Maximum
Capacity (Btu/h)
Power Usage
(w) EER
Maximum
Capacity (Btu/h)
Power Usage
(w) EER
14
O
F (-10
O
C)* 12,870 825 15.60 13,138 795 16.53 13,406 764 17.55
32
O
F (0
O
C) 12,845 834 15.40 13,112 803 16.33 13,380 772 17.33
50
O
F (10
O
C) 12,819 842 15.22 13,086 811 16.14 13,353 780 17.12
65
O
F (18
O
C) 12,794 851 15.03 13,060 820 15.93 13,327 788 16.91
75
O
F (24
O
C) 12,669 860 14.73 12,933 828 15.62 13,197 796 16.58
85
O
F (29
O
C) 12,543 868 14.45 12,805 836 15.32 13,066 804 16.25
95
O
F (35
O
C) 12,096 1,102 10.98 12,348 1,061 11.64 12,600 1,020 12.35
105
O
F (41
O
C) 11,733 1,112 10.55 11,978 1,071 11.18 12,222 1,030 11.87
115
O
F (46
O
C) 11,491 1,123 10.23 11,731 1,082 10.84 11,970 1,040 11.51