Submittals
Next Gen Arctic Series Submittal
Rev. Feb 2021
12000 BTU/HR MID-STATIC DUCTED INVERTER DRIVEN HEAT PUMP SYSTEM
1U12EH2VHE / USYM12UCDSA
Job Name: __________________________________
Purchaser: __________________________________
Submitted To: _______________________________
Construction: _______________________________
Reference: __________________________________
Approval: ___________________________________
Date: ______________________________________
Submitted By: _______________________________
Unit: _______________________________________
Drawing #: __________________________________
Electrical Requirement
Power Supply
208/230V, 1 Phase,
60 HZ
Operating Voltage Range 187~253 VAC
Recommended Fuse/Breaker Size 20A
MCA 14A
Cooling Performance
Rated Cooling Capacity 12,000 BTU
Cooling Capacity Range 3,100~13,600 BTU
Rated Power input 950 W
SEER 20.0
EER 12.5
Moisture Removal 3.2 Pt./h
Heating Performance
Rated Heating Capacity 14,500 BTU
Heating Capacity Range 3,100~21,000 BTU
Rated Power Input 1,500 W
HSPF 10.5
CUS
Intertek
For more information visit us:
www.Haierductless.com
www.Haierductlesshelp.com
Connecting cable to indoor units must be 14/4 AWG unshielded stranded
copper. Cable must be ran continuous, without splicing.
Accessories
Pipe Length
Minimum Pipe Length 10 ft
Maximum Pipe Length 50 ft
Maximum Pipe Height Dierence 33 ft
Flare Connections
Liquid
Outdoor: 3/8”*
Indoor: 1/4”*
Vapor 1/2”
*use adaptor shipped with outdoor unit
Wired Controller
Controller must be ordered separately.
Compatible with the Simplied (QACT17A) and
Programmable (YR-E16B) wall controllers.
Built-in WiFi
Supply Plenum
UAPT0912A
Filter Box
UAMFB0912A
Operating Range
Cooling With Wind Bae 14~115°F (-10~46°C)
Cooling Without Wind Bae 23~115°F (-5~46°C)
Heating -31~75°F (-35~24°C)