Submittals

Next Gen Arctic Series Submittal
Rev. Feb 2021
Electrical Requirement
Power Supply
208/230V, 1 Phase,
60 HZ
Operating Voltage Range 187~253 VAC
Recommended Fuse/Breaker Size 20A
MCA 14A
Cooling Performance
Rated Cooling Capacity 12,000 BTU
Cooling Capacity Range 3,100~15,000 BTU
Rated Power input
800 W
SEER 27.0
EER 15.0
Moisture Removal 3.4 Pt./h
Heating Performance
Rated Heating Capacity 14,500 BTU
Heating Capacity Range 3,100~22,000 BTU
Rated Power Input
1,400 W
HSPF 13.0
CUS
Intertek
Accessories
12000 BTU/HR HIGHWALL INVERTER DRIVEN HEAT PUMP SYSTEM
1U12EH2VHE / AW12EH2VHD
For more information visit us:
www.Haierductless.com
www.Haierductlesshelp.com
Connecting cable to indoor units must be 14/4 AWG unshielded stranded
copper. Cable must be ran continuous, without splicing.
Job Name: __________________________________
Purchaser: __________________________________
Submitted To: _______________________________
Construction: _______________________________
Reference: __________________________________
Approval: ___________________________________
Date: ______________________________________
Submitted By: _______________________________
Unit: _______________________________________
Drawing #: __________________________________
Pipe Length
Minimum Pipe Length 10 ft
Maximum Pipe Length 50 ft
Maximum Pipe Height Dierence 33 ft
Flare Connections
Liquid 1/4”
Vapor 1/2”
Remote Controller
Ships with Motion Sense Remote (WJ26X27153)
Wired Controller
Compatible with the Simplied (QACT17A) and
Programmable (YR-E16B) wall controllers.
Wind Bae
Uses wind bae QAWB37A
Built-in Features
WK-B wired controller adapter
WiFi
Occupancy sensor
Operating Range
Cooling With Wind Bae 14~115°F (-10~46°C)
Cooling Without Wind Bae 23~115°F (-5~46°C)
Heating -31~75°F (-35~24°C)