6. Electric characteristics
Symbols:
MCA: Min. circuit amps (A)
MFA: Max. fuse amps of circuit breaker Output: Fan motor rated output (w) FLA: Full load amps (A)
Notes:
1. Voltage range
The units are applicable for the electrical systems where voltage supplied to unit is in the range.
2. Maximum allowable voltage unbalance between phases is 2%.
3. MCA=1.25*FLA MFA≤4*FLA.
4. Power supply uses the circuit breaker.
Units Power supply Indoor fan motor Power input (W)
Model Phase FQY Voltage
Volt.
range
MCA MFA
Output
(W)
FLA Cooling Heating
MVAW007MV2AA 1 50/60 220 198~242 0.18 0.56 30 0.14 43 43
MVAW009MV2AA 1 50/60 220 198~242 0.18 0.56 30 0.14 43 43
MVAW012MV2AA 1 50/60 220 198~242 0.18 0.56 30 0.14 43 43
MVAW018MV2AA 1 50/60 220 198~242 0.24 0.76 40 0.19 57 57
MVAW024MV2AA 1 50/60 220 198~242 0.24 0.76 40 0.19 57 57
MVAW030MV2AA 1 50/60 220 198~242 0.4 1.28 70 0.32 99 99