Service Guide

30
11. Dip switch setting
In the following table,1 represents ON and 0 represents OFF.
Denition principles of code switches:
SW01 is used to set wire controlled address of and set capabilities of master; SW03 is used to set indoor unit
address (combine original communication address and address of centralized controller).
(A) Denition and description of SW01
Note: A wired controller can connected to at most sixteen ultrathin indoor units.
SW01_1
SW01_2
SW01_3
SW01_4
Address of
wire controlled
indoor unit
(group
address)
[1] [2] [3] [4] Address of wire controlled indoor unit (group address)
0 0 0 0 0#(wire controlled master unit)(default)
0 0 0 1 1#(wire controlled slave unit)
0 0 1 1 2#(wire controlled slave unit)
0 0 1 1 3#(wire controlled slave unit)
... ... ... ... ......
1 1 1 1 15#(wire controlled slave unit)
SW01_5
SW01_6
SW01_7
SW01_8
Capability of
indoor unit
[5] [6] [7] [8] Capability of indoor unit
0 0 0 1 0.8HP(MVAW007MV2AA)
0 0 1 0 1.0HP(MVAW009MV2AA)
0 0 1 1 1.2HP(MVAW012MV2AA)
0 1 1 0 2.0HP(MVAW018MV2AA)
0 1 1 1 2.5HP(MVAW024MV2AA)
1 0 0 1 3.2HP(MVAW030MV2AA)