Service Guide

22
Connection of indoor drain hose
1. Please use the accessory drain hose to connect indoor unit's water outlet and PVC pipe. Use snap rings to
tighten them as shown in the following gure:
2. Please use rigid PVC adhesive for connection of other pipes and ensure there is no leakage.
3. Drain hose must be wrapped with insulation sleeve and tightened with a strap to prevent air leakage from
producing condensate.
4. To prevent water owing back into air conditioner when the unit stops running, drain hose should decline to
the drainage side with an inclination of above 1/100. Drain hose expansion or water accumulation should be
prevented, or else it will cause abnormal noise.
5. When connecting the drain hose, do not pull on it to avoid the pipe connections from getting loose or
disconnected. Drain hose should not be pulled out laterally for more than 8in(200mm) and should be supported
every 31-39in(0.8-1.0m) to avoid bending.
6. The end of drain hose should be more than 2in(50mm) away from the ground or the bottom of drainage tank. It
should not be put in water. To directly drain condensate into drainage ditch, the drain hose must be U-shaped to
avoid smell from entering through the hose into room.
Drainage test
Before the test, ensure the drain hose is clear and all connections
are tightly sealed.
Then perform the drainage test as follows:
1. Add about 0.132gal (500ml) of water into the water pan through
water injection hole.
2. Switch on the power and operate the unit in cooling mode.
Check that the water outlet drains water normally and that there
are no leakages at the connections. After the drainage test is
complete, replace the water injection hole plug. For the position
of water injection hole, see the gure on the right:
Set a supporting point at every 31-39in(0.8-1.0m)
8in(200mm)
24in
(600mm)
2
-
4in(50-100mm)
2
-
4in(50-100mm)
8in(200mm)
8in(200mm)
27.5in(700mm)
27.5in(700mm)
Installation of drain hose