Service Guide
Table Of Contents
20
This series of air conditioners can be arranged in two air return modes: 1. Air return from the back (Factory default);
2. Air return from the bottom (can be adjusted on site. See the following gures.)
Note:
The downward air return mode will increase noise 3-5dB(A). It is recommended to install the air conditioner in
downward return air mode 2 if enough space is available.
Air return from the bottom 1Air return from the back Air return from the bottom 2
Installation modes of Indoor unit
Installation space and method
Dimensions of return air inlet
h
Hanger dimensions
b
a
c
Dimensions of air outlet
d
f
g
e
Air in
Dimensions of pump drainage
hole, OD Ø1"
Dimensions of natural
drainage hole, OD Ø1"
Dimensions of drain hose
Body installation
1.Use 3/8" (M10) lifting bolts.
2.Ceiling removal: For different building structures, please consult with building personnel about actual conditions.
a. Ceiling reinforcement: Ensure the ceiling is horizontal and will not shake. The ceiling base frame must be
reinforced.
b. Cut off and remove the ceiling base frame.
c. Reinforce the faces left when the ceiling is removed and further reinforce the base frame that x both ends of the
ceiling.
d. After the unit installation is complete, it is time to install pipes and wires. Before installation, choose a suitable
installation position and determine the outgoing direction of pipes. Especially in case that a ceiling exists, please
pull refrigerant tubing, drain hose, indoor and outdoor connecting wires, control wires to their connection positions
prior to hanging the machine.
Model a b c d e f g h i
MVAD007~12MV2AA 16.5 35.1 14.6 33.5 7.3 25.2 3.6 29.9 6.0
MVAD018~24MV2AA 16.5 47.7 14.6 46.1 7.3 37.8 3.6 42.5 6.0
Dimension (unit: in.).