Service Guide
Table Of Contents
9
6. Electric characteristics
Units Power supply Indoor fan motor Power input (w)
Model Phase FQY Voltage Volt range MCA MFA Output (W) FLA Cooling Heating
MVAD007MV2AA 1 50/60 220 198-242 0.24 0.76 50 0.19 31 31
MVAD009MV2AA 1 50/60 220 198-242 0.24 0.76 50 0.19 31 31
MVAD012MV2AA 1 50/60 220 198-242 0.38 1.2 50 0.3 31 31
MVAD018MV2AA 1 50/60 220 198-242 0.38 1.2 45 0.47 40 40
MVAD024MV2AA 1 50/60 220 198-242 0.59 2.12 45 0.53 50 50
Symbols:
MCA: Min. circuit amps (A)
MFA: Max. fuse amps of circuit breaker Output: Fan motor rated output (w) FLA: Full load amps (A)
Note:
1. Voltage range
The units are applicable for the electrical systems where voltage supplied to unit is in the range.
2. Maximum allowable voltage unbalance between phases is 2%.
3. MCA=1.25*FLA MFA≤4*FLA
4. Power supply uses the circuit breaker.