11. Dip switch setting
Denition principles of code switches:
SW01 is used to set wire controlled address of and set capabilities of master; SW03 is used to set indoor unit
address (combine original communication address and address of centralized controller).
(A) Denition and description of SW1
SW1_1
SW1_2
SW1_3
SW1_4
Address of wire
controlled indoor
unit
[1] [2] [3] [4] Address of wire controlled indoor unit (group address)
OFF OFF OFF OFF 0# (wire controlled master unit) (default)
OFF OFF OFF ON 1# (wire controlled slave unit)
OFF OFF ON OFF 2# (wire controlled slave unit)
OFF OFF ON ON 3# (wire controlled slave unit)
OFF ON OFF OFF 4# (wire controlled slave unit)
OFF ON OFF ON 5# (wire controlled slave unit)
∙∙∙ ∙∙∙ ∙∙∙ ∙∙∙ ∙∙∙
ON ON ON ON 15# (wire controlled slave unit)
SW1_5
SW1_6
SW1_7
SW1_8
Capability of
indoor unit
[5] [6] [7] [8] Capability of indoor unit
OFF OFF ON OFF 9000BTU (MVAB009MV2AA)
OFF OFF ON ON 11000BTU (MVAB012MV2AA)
OFF ON ON OFF 18000BTU (MVAB018MV2AA)
(B) Denition and description of SW3
Note *:
Set the address by code when connecting the centralized controller or gateway or charge system.
Address of centralized controller=communication address+0 or+64.
SW3_ 2=OFF, address of centralized controller=communication address+0=communication address
SW3_ 2=ON, address of centralized controller=communication address+64 (applies when centralized controller is used
and there are more than 64 indoor units)
To use with 0010451181A in use, it is required to use code for address setting. Set SW3_1=0N
and SW3_ 2=OFF; SW3_3, SW3_ 4, SW3_5, SW3_6, SW3_7 and SW3_ 8 are address codes which are set according
to actual address.
Address setting function of wired controller for ultrathin card machine is disabled.
SW3_1
Address setting
mode
[1] Address setting mode
OFF Automatic setting (default)
ON Setting address by dip switch
SW3_2
~
SW3_8
Code-set indoor
unit address
and centralized
controller address
(Note *)
[2] [3] [4] [5] [6] [7] [8] Address of indoor unit
Address of centralized
controller
OFF OFF OFF OFF OFF OFF OFF 0# (Default) 0# (Default)
OFF OFF OFF OFF OFF OFF ON 1# 1#
OFF OFF OFF OFF OFF ON OFF 2# 2#
OFF ON ON ON ON ON ON 63# 63#
ON OFF OFF OFF OFF OFF OFF 0# 64#
ON OFF OFF OFF OFF OFF ON 1# 65#
ON OFF OFF OFF OFF ON OFF 2# 66#
ON ON ON ON ON ON ON 63# 127#