Owners Manual

49-5000255 23
ENGLISH
INITIAL SETTING
SW03_2
~
SW03_8
The
communication
address of
indoor unit
address
[2] [3] [4] [5] [6] [7] [8]
Communication
address
Center controller
address
1 0 0 0 0 0 0 0# 64#
1 0 0 0 0 0 1 1# 65#
1 0 0 0 0 1 0 2# 66#
…… ……
1 1 1 1 1 1 0 62# 126#
1 1 1 1 1 1 1 63# 127#
NOTES:
The unit address setting is written in the chip during power up of the connection kit.
1. Make sure that the unit address code is set before the connection kit is energized.
a. Dip switch setting by hand when connected to the controller, gate way and BMS
b. Dip switch setting method as below:
SW03_2 = OFF, central controller address = communication address + 0 = communication address
SW03_2 = ON, central controller address = communication address + 64= communication address
c. In the system, when PCB code of indoor unit is 0010451181A, you must use dip switchs for address setting.
SW03_1=ON, SW03_2=OFF, SW03_3/SW03_4/SW03_5/SW03_6/ SW03_7/SW03_8 are address No.
d. The corresponding relation of connection kits address and indoor communication address
MS1 connection kit address= indoor communication address;
MS3 connection kit address= indoor A communication address,
MS3 connection kit address +1= indoor B communication address
MS3 connection kit address +2= indoor C communication address
Example: a system contains four connection kits (such as No. 1, No. 2, No. 3, No. 4), then connection kit address
can be set as follows:
MS1
No. 1
MS1 address Indoor address
0# 0#
MS3 address Indoor A address Indoor B address Indoor C address
MS3
No. 2
1# 1# 2# 3#
MS3
No. 3
4# 4# 5# 6#
MS3
No. 4
7# 7# 8# 9#
Example
Indoor unit address
DIP VB 1 VB 2 VB 3 VB 4 VB 5
SW 01 11100000 10000000 10100000 10000000 01100000
SW 03 10000000 10000011 10000100 10000110 10000111
Address 0 3 4 6 7