Owners Manual

49-5000255 21
ENGLISH
INITIAL SETTING
Operate according to the following setting as necessary after refrigerant piping construction and electrical wiring construction
are completed.
1. The choice of indoor unit:
SW01 is used for INDOOR UNIT. Position 1 is on, and position 0 is off.
SW01_1 Indoor unit A
0 not present
1 present
SW01_2 Indoor unit B
0 not present
1 present
SW01_3 Indoor unit C
0 not present
1 present
SW01_4 ~ SW01_8 Factory Seting 0 Default Setting
2. Code setting for the unit address of the connection kit:
SW03 is used for MS devices address setting, 1 is ON, 0 is OFF
SW03_1
Manner of set
address
0 Set the address with automatism
default
1 Set the address with dip switch
SW03_2
~
SW03_8
The
communication
address of
indoor unit
address
[2] [3] [4] [5] [6] [7] [8]
Communication
address
Center controller
address
0 0 0 0 0 0 0 0#
default
0#
default
0 0 0 0 0 0 1 1# 1#
0 0 0 0 0 1 0 2# 2#
0 0 0 0 0 1 1 3# 3#
0 0 0 0 1 0 0 4# 4#
0 0 0 0 1 0 1 5# 5#
0 0 0 0 1 1 0 6# 6#
0 0 0 0 1 1 1 7# 7#
0 0 0 1 0 0 0 8# 8#
0 0 0 1 0 0 1 9# 9#
0 0 0 1 0 1 0 10# 10#
0 0 0 1 0 1 1 11# 11#
0 0 0 1 1 0 0 12# 12#
0 0 0 1 1 0 1 13# 13#
0 0 0 1 1 1 0 14# 14#
0 0 0 1 1 1 1 15# 15#
0 0 1 0 0 0 0 16# 16#
0 0 1 0 0 0 1 17# 17#
0 0 1 0 0 1 0 18# 18#
0 0 1 0 0 1 1 19# 19#
0 0 1 0 1 0 0 20# 20#
0 0 1 0 1 0 1 21# 21#
0 0 1 0 1 1 0 22# 22#
0 0 1 0 1 1 1 23# 23#
0 0 1 1 0 0 0 24# 24#