ELECTRICAL WIRING
Connection Kit Power and Control Wiring
Power and control wire specifications
The currant rating of the connection kit is 0.15A (not
including indoor units)
Power and communication wiring must be properly
secured
All connection kits must have a proper earth ground.
Increase power wiring size per NEC code requirements
according to length.
Communication ground should only be grounded at the
outdoor unit and should not come in contact with ground
at any other point.
Communication wire total length cannot exceed 3280 ft.
Wiring Diagram
Communication wires should be connected at the outdoor unit terminal block on terminals P and Q. Communication wires
may “daisy Chain” to other connections kits in this manner.
Items
Total
Current
of valve
boxes
(
A)
Cross
Section
gauge
Length
ft
Rated
Current of
Breaker
(A)
Rated Current of Power
Leakage Breaker (A)
Leaking Current (mA)
Operating Period (S)
Cross Sectional Area of
Signal Line
Outdoor -
connection
kit (ga)
Connection
kit -
connection
kit (ga )
<10 14 20 20 20A,30mA,0.1S or below
16 twisted-shielded
with ground
≥10 and <15 12 25 30 30A,30mA, 0.1S or below
≥15 and <22 10 30 40 40A,30mA, 0.1S or below
≥22 and <27 8 40 50 50A,30mA, 0.1S or below