Installation Guide
23
evacuation
degree.
Evacuate
Installation Procedure 
Piping vavuum method: to use vacuum pump 
1. 
Detach the service port's cap 
of 
3-way valve, the valve rod's cap for 2-way 
valve and 3-way valves, and connect the service port into the projection 
of 
charge hose (low) for gaugemanifold. Then connect the projection 
of 
charge 
hose (center) for gaugemanifold into vacuum pump. 
2. Open the handle at low 
in 
gaugemanifold, and operate vacuum pump. If the 
scale-moves 
of 
gause (low) reach vacuum condition 
in 
a moment, check 
the step 1 again. 
3. Vacuumize for over 15min.  check the level gauge which should read -
0.1 
MPa (-76 cm Hg) at low pressure side. After the completion 
of 
close the handle 'Lo' 
in 
the vacuum pump. Check the condition 
of 
the scale 
and hold it for 1-2min. If the scale-moves back 
in 
spite 
of 
tightening, make 
flaring work again, then return to the beginning 
of 
the step 3. 
4. Open the valve for the 2-way valve to an angle 
of 
anticlockwise 90 
After 6 seconds, close the 2-way valve and make the inspection 
of 
gas leakge. 
2wayvalve 
~ 
3wayvalve 
~ 
Vacuuming 
Liquid stop valve 
Gas stop valve 
Vacuum pump 
5. No gas leakage? 
In 
case 
of 
gas leakage, tighten parts 
of 
pipe connection. If leakage stops, then proceed the step 6.  If it 
does not stop gas leakage, discharge whole refrigerants from the service port. After flaring work again, fill up prescribed 
refrigerant from the gas cylinder. 
6. Detach the charge hose from the service port, open 2-way valve and 3-way. 
Turn the valve rod anticlockwise until hitting lightly. 
7. 
To 
prevent the gas leakage, turn the service ports cap, the valve rodis cap 
for 2-way valve and 3-way's a little more than the point where the torque 
increases suddenly. 
CAUTION: 
If the refrigerant 
of 
the air conditioner leaks, it is necessary to make all the refrigerant out. 
the liquid refrigerant into air conditioner according to the amount marked on the nameplate. 
llw 
2wyv~IVr 
c 
3 wa
1 
valve  \  , 
I 
Ii 
I 
I~ 
l£;;:? 
'. 
,0 
Valve rod  cap 
~ 
6 Valve rod cap 
rP 
Service port cap 
first, then charge 