Installation Guide
• Electrical Safety Requirements
Note:
1. The  surrounding  conditions  (ambient  temperature,  direct  sunlight  and  rainwater)  shall  be  noticed  during
electrical wiring, with effective protective measures being taken.
2. Copper wire cable in line with local standards shall be used as the power line and connector wire.
3. Both the indoor unit and outdoor unit shall be reliably earthed.
4. Wiring  for  the  outdoor  unit  shall  be  made  first  and  then  the  indoor  unit.  The  air  conditioner  can  only  be
powered on after wiring and pipe connection.
5. The dedicated branch circuit must be used, and leakage protector with sufficient capacity must be installed.
• Qualification Requirements of Installer
Relevant qualification certificate must be obtained as per national laws and regulations.
• Indoor Unit In
stallation
1. Fixation of wall panel and piping layout
In case of left/right water pipe connection for the indoor unit, or in case the evaporator interface of the indoor
unit  and  the  horn  mouth  of  the  connecting  piping  cannot  be  extended  to  the  outdoor  side  for  installation,  the 
connector  pipes  shall  be  connected  to  the  evaporator  piping  interface  of  the  indoor  unit  in  the  process  of  horn 
mouth. 
2. Piping layout
During layout of connecting pipes, drain hose and connector wires, the drain hose and connecting wire shall
be placed at the bottom and top respectively. The power line cannot be twined with the connector wire. The drain 
pipes (especially inside the room and mach
ine) must be ventilated with thermal insulation materials.  
3. Nitrogen charging for pressure maintaining and leak detection
After the evaporator of the indoor unit is connected to the connector pipe (after welding), nitrogen more than
4.0MPa  shall be  charged inside  the  evaporator and  the  piping  connected to evaporator  with  a nitrogen  cylinder 
(adjusted by a reducing valve). Afterwards, the valve of the nitrogen cylinder shall be closed, for leak detection
with soapy water or leak detecting solution. The pressure shall be maintained for more than 5 minutes, and then 
whether the system pressure is reduced or not shall be observed. In case the pressure is reduced, leakage can be 
identifie
d. After the leak point is handled, the steps above shall be repeated. 
After  the  evaporator  of  the  indoor  unit  is  connected  to  connecting  piping,  nitrogen  shall  be  charged  for 
pressure maintaining and leak detection. Afterwards, the evaporator shall be connected to the two-way stop valve 
and three-way stop valve of the outdoor unit. After the copper cap of the connecting piping is fastened, nitrogen 
more than 4.0MPa shall be charged at the access hole of the three-way stop valve with a charging hose. The valve 
of  the  nitrogen  cylinder  shall  be  closed,  for  leak  detection  with  soapy  water  or  leak  detecting  solution.  The 
pressu
re shall be maintained for more than 5 minutes, and then whether the system pressure is reduced or not shall 
be observed. In case the pressure is reduced, leakage can be identified. After the leak point is handled, the steps 
above shall be repeated. 
The operation above can also be completed after the indoor unit is connected to the connecting pipelines and 
the two-way stop valve and three-way stop valve of the outdoor unit, after the access hole of the outdoor unit is 
connected to the nitrogen cylinder and pressure gauge and after more than 4.0MPa nitrogen is charged. No leak 
points  are  identified  in  the  leak  detection  at  the  joint/welding  junction  of  the  indoor  unit  and  at  the  join
t  of 
connecting  pipelines  of  the  two-way  stop  valve  and  three-way  stop  valve  of  the  outdoor  unit.  It  must  be 
guaranteed that each joint is available for leak detection during installation. 
The next step (vacuumizing with a vacuum pump) can only be continued after the installation steps (nitrogen 
charging for pressure maintaining and leak detection normal) are completed. 
• Outdoor Unit Installation
1. Fixation and connection
Note:
a) Fire source shall be avoided within 3m around the place of installation.
b) The leak detection equipment of refrigerant shall be placed at a low position in the
outdoor, and shall be opened.