Installation Guide
Amax Bmax
C D
21
10
15
10
20
20
1.
Outdoor unit
Indoor unit
A
B
Outdoor unit
Indoor unit
A
B
A
B
Outdoor unit
Indoor unit
Oil trap
When bending the pipe, be careful not to crush it. To prevent breaking of the pipe, avoid sharp bends. 
Bend the pipe with a radius of curvature of 40 mm or over.
Connecting the pipe of gas side
rst makes working easier.
The connection pipe is specialized for R32.
Half union
Flare nut
Forced fastening without careful centering may
damage the threads and cause a leakage of gas.
Pipe Diameter( ) Fastening torque
Liquid side6.35mm(1/4") 18N.m
Liquid/Gas side9.52mm(3/8") 42 N.m
Gas side 12.7mm(1/2") 55N.m
Connection of pipes
Spanner 
Torque wrench 
Gas side 15.88mm(5/8")  60 N.m
Be careful that matters, such as wastes of sand
s,water,
, etc. shall not enter the pipe.
CAUTION
The standard pipe length is Cm. If the pipe 
has 
to be lengthened, the refrigerant should be charged, 
according to D g/m. But the charge of refrigerant 
must 
be conducted by profes
sional air conditioner 
engineer. Before adding additional refrigerant, 
perform air  purging from the refrigerant pipes and indoor 
unit using a vacuum pump,then  charge additional refrigerant.
2.
Max.Elevation: 
Amax
In case the elevation A is more 
than 5m, oil trap shoud be 
installed every 5~7
Max. Length: 
Bmax
M i n. Length: 
B min
In case the pipe length B is 
more than Cm, the refrigerant 
should be charged, according 
to  D g/m.
Bmin
3
3
10
1U26MADFRA
1U35MADFRA
FOR 
FOR 
1U53WADFRA 
1U71WADFRA
AS26PBDHRA/1U26MADFRA
AS35PBDHRA/1U35MADFRA
AS53PDDHRA/1U53WADFRA 
AS71PDDHRA/1U71WADFRA
Installation Procedure 
Piping size 
• 
• 
• 
Liquid pipe 
Gas pipe 
Liquid pipe 
Gas pipe 
• 
• 
• 
• 
• 
fi 
cp 
6.35x0.8mm 
cp 
9.52x0.8mm 
cp 
6.35x0.8mm 
cp 
12.7x0.8mm 
L 
Piping Connection 
•  Install the removed flare nuts to the pipes 
to be connected, then flare the pipes . 
0 
Outdoor 
Unit 
15  25 