Installation Guide
3
R32
R32
R32
R32
R32
R32
R32
18
Read Before Installation 
Piping Materials 
Types 
of 
Copper Pipes (Reference) 
Maximum Operation Pressure  Applicable Refrigerants 
3.4MPa 
R22,R407C 
4.  MPa 
•  Use pipes that meet the local standards. 
Piping Materials/Radial Thickness 
Use pipes made 
of 
phosphorus deoxidized copper. 
Since the operation pressure 
of 
the units that use  is 
hig_her 
than that 
of 
the units for use with R22,  use pipes with 
at least the radial thickness specified 
in 
the chart below. (Pipes with a radial thickness 
of 
0.7mm 
or 
less may not be used.) 
Size(mm)  Size(inch)  Radial Thickness(mm) 
Type 
cp6.35  1/4"  0.8t 
cp9.52  3/8"  0.8t 
Type-O pipes 
cp 
12.7  1/2"  0.8t 
C/) 
15.88 
5/8"  1.0t 
C/) 
19.05  3/4"  1.0t  Type-1/2H 
or 
Hpipes 
•  Although it was possible to use type-O for pipes with a size 
of 
up 
to 
c/) 
19.05(3/4") with conventional refrigerants, use type-
1 /2H pipes for units that use  .(Type-O pipes may be used if the pipe size 
is 
c/)19.05 
and the radial thickness is 1.2t.) 
•  The table shows the standards 
in 
Japan. Using this table as a reference, choose pipes that meet the local standards. 
Flare Machining (type-O and OL only) 
The flare machining dimensions for units that use 
air tightness. 
Flare Machining Dimension(mm) 
External dimension 
of 
pipes 
Size 
Dimension A 
<P6.35 
1/4" 
9.1 
<P9.52 
3/8"  13.2 
<P12.7 
1/2" 
16.6 
<P15.88 
5/8"  19.7 
<P19.05 
3/4"  24.0 
is larger than those for units that use R22 
in 
order to increase 
R22 
9.0 
13.0 
16.2 
19.4 
23.3 
If a clutch type flare tool is  used to machine flares 
on 
units that use  , make the protruding part 
of 
the pipe between 
1.0 and  1.5mm. Copper pipe gauge for adjusting the length 
of 
pipe protrusion is useful. 
Flare Nut 
Type-2 flare nuts instead 
of 
type-1  nuts are used to increase the strength. The size of some 
of 
the flare nuts have also 
been changed. 
Flare nut dimension(mm) 
External dimension 
of 
pipes  Size 
Dimension B 
(Type2)  R22(Type1) 
<P6.35 
1/4"  17.0  17.0 
<P9.52 
3/8" 
22.0 
22.0 
<P12.7 
1/2"  26.0  24.0 
ED~ 
<P15.88 
5/8" 
29.0  27.0 
Dimension B 
<P19.05 
3/4"  36.0  36.0 
•  The table shows the standards 
in 
Japan. Using this table as a reference, choose pipes that meet the local standards. 