Spec Sheet

31-5000409 Rev. 0 9
ENGLISH
SYSTEM
Part 1: General
1.1 Description
A. The Haier FlexFit Multi heat pump air conditioner shall be a variable capacity, mini-split type system comprised
of a single outdoor and up to four indoor units.
B. The FlexFit Multi heat pump air conditioner shall be compatible with any FlexFit indoor unit. See combination
chart for matching indoor capacity types with an outdoor system.
1.2 Toxicity
A. The heat pump system shall participate in RoHS compliance and listed in the directory.
Part 2: Performance and Operating Range
2.1 Operating Range
A. The heat pump unit shall provide cooling within the ambient temperature range of 0°~115°F (-18°C~46°C).
B. The heat pump shall operate normally with voltages between 187~253V.
2.2 Performance
The system shall perform within the specified operating window found on the following table.
A. Cooling performance rating shall be verified following AHRI 210/240 standards of 80°F DB/67°F WB (27°/19°C)
indoor temperature and 95°F DB/75°F WB (35°/24°C) outdoor temperature.
B. Heating performance rating shall be verified following AHRI 210/240 standards of 70°F DB/60°F WB (21°/16°C)
indoor temperature and 47°F DB/43°F WB (8°/6°C) outdoor temperature.