Spec Sheet

31-5000409 Rev. 0 17
ENGLISH
DUCTED INDOOR UNITS
Part 1: General
1.1 Description
A. The ducted indoor unit completes the system when connected to the matching outdoor unit and field-supplied
piping and wiring.
1.2 Warranty
A. The ducted indoor unit shall be covered by a manufacture parts warranty. See appendix for full warranty detail.
1.3 Sound Pressure Rating
Model Blower Pressure Sound Rating dB(A)
(turbo/high/medium/low/quiet)
AD07SL2VHB 35/33/29/26/21
AD09SL2VHB 35/33/29/26/22
AD12SL2VHB 38/35/29/26/23
AD18SL2VHB 31/29/23/29/25
AM24LP2VHA 38/35/32/29/--
Part 2: Installation Requirements
2.1 Condensate
A. The ducted indoor unit shall ship with an insulated drain tube adapter that is sized for 3/4-inch PVC on one end.
B. The ducted indoor unit shall have gravity drain ports on both sides of the unit.
2.2 Clearances
A. The installer must follow the minimum clearances illustrated in the installation manual when installing the
indoor unit.
2.3 Mounting
A. The ducted indoor unit shall have 4 hanging brackets that are sized for 3/8 threaded rod.
B. The installer must use 3/8 threaded rod to suspend the ducted indoor unit from the building structure.
C. The installer must install the unit upright and level in all directions.
Part 3: Electrical Requirements
3.1 Electrical Disconnect
A. Connecting wire must be continuous, without break, unless local code requires power disconnect next to
indoor unit.
Model Fan Motor Rating (HP)
AD07SL2VHB 0.066
AD09SL2VHB 0.066
AD12SL2VHB 0.085
AD18SL2VHB 0.114
AM24LP2VHA 0.362
B. If a disconnect is required by local code, it must be a 3-pole, single-throw type.