Submittals
FlexFit Multi Series Submittal
Rev. Mar. 2021
Cooling Performance
Cooling Capacity Range 4,400~19,400 BTU
Rated Power Input
(Non-Ducted/Ducted)
1,650/1,760 W
SEER (Non-Ducted/Ducted) 16.0/16.0
EER (Non-Ducted/Ducted) 10.5/8.5
Heating Performance
Heating Capacity Range 6,100~21,5000 BTU
HSPF (Non-Ducted/Ducted) 9.0/.8.5
CUS
Intertek
Accessories
18000 BTU/HR INVERTER DRIVEN MULTI-ZONE HEAT PUMP SYSTEM
2U18MS2VHB
Outdoor Unit
Compressor DC inverter Driven Rotary
Uncrated Dimension (HxWxD)
27 1/8 x 31 7/8 x 11 3/8 in
(688 x 810 x 288 mm)
Crated (HxWxD)
29 7/8 x 37 3/8 x 16 in
(760 x 949 x 406 mm)
Outdoor Sound Rating dB 53
Heat Exchanger Fin Type Blue Fin
Weight (Ship/Net) 102.5/95.9 lbs
Factory Refrigerant Charge R-410A (49.5 oz)
2U18MS2VHB
11 3/8 (288)
27 1/8 (688)
31 7/8 (810)
Electrical Requirement
Power Supply 208/230V, 1 Phase, 60 HZ
Operating Voltage Range 187~253 VAC
Recommended Fuse/Breaker Size 25A
MCA 15A
Operating Range
Cooling 14~115°F (-10~46°C)
Heating -4~75°F (-20~24°C)
Pipe Length
Minimum Pipe Length (Each) 6 ft
Maximum Pipe Length (Each/All) 65 ft /98 ft
Pre-Charged 50 ft
Additional Charge 0.2 oz/ft
Maximum Pipe Height Dierence 50 ft
Flare Connection
1/4”, 1/4”(Discharge)
3/8”, 3/8” (Suction)
For more information visit us:
www.Haierductless.com
www.Haierductlesshelp.com
Wind Bae
Uses wind bae QAWB43A
Connecting cable to indoor units must be 14/4 AWG unshielded stranded
copper. Cable must be ran continuous, without splicing.
Job Name: __________________________________
Purchaser: __________________________________
Submitted To: _______________________________
Construction: _______________________________
Reference: __________________________________
Approval: ___________________________________
Date: ______________________________________
Submitted By: _______________________________
Unit: _______________________________________
Drawing #: __________________________________
Floor Mounting
Dimensions
4 1/2
(114)
23
(584)
4 1/2
(114)
12 5/8
(321)