Spec Sheet

Multi-Zone Indoor Units Multi-Zone Indoor Units
Haier FlexFit multi-zone systems can operate from 2 to 4 indoor units simultaneously, with
individual zone control.
- Choose any type of unit: wall mount, duct, or cassette
- Cooling at 115F and heating at -4F
- Blue fin coating for both indoor and outdoor coil protection and performance enhancement
- Whisper quiet operation
Haier FlexFit ductless systems feature mixing and matching the same indoor units
to both single-zone and multi-zone outdoor units.
Highwall Indoor AW07LC2VH*1 AW09LC2VH*1 AW12LC2VH*1 AW18LC2VH*1 AW24LP2VH*
Rated Cooling Capacity Btu/hr 7,000 9,000 12,000 18,000 22,000
Rated Heating Capacity Btu/hr 8,000 10,000 13,000 19,000 24,000
Voltage, Cycle, Phase V/Hz/- 208-230/60/1 208-230/60/1 208-230/60/1 208-230/60/1 208-230/60/1
Airflow (Turbo/H/M/L/Quiet) CFM 410/350/295/235/205 410/350/295/235/205 440/380/320/265/215 636/530/483/430/383 710/650/560/440/410
Indoor Sound dB (Turbo/H/M/L/Quiet) 43/38/33/26/22 43/38/33/26/22 44/39/34/27/23 48/45/40/35/30 49/47/42/36/34
Dimension: H x W x D in (mm)
11 x 33 5/8 x 8 1/16 (280 x 855 x 204)
12 3/4 x 39 1/4 x 9 1/4
(332 x 997 x 235)
13 1/4 x 43 7/8 x 9 9/16
(336 x 1115 x 243)
Weight (Ship/Net)- lbs (kg) 26.8/22(12.2/10) 35.3/28.6 (16/13) 45.4/37.5 (20.6/17)
Liquid /Suction O.D. in 1/4 3/8 1/4 3/8 1/4 3/8 1/4 1/2 3/8 5/8
Duct Indoor AD07SL2VH* AD09SL2VH* AD12SL2VH* AD18SL2VH* AM24LP2VH*
Rated Cooling Capacity Btu/hr 7,000 9,000 12,000 18,000 24000
Rated Heating Capacity Btu/hr 8,000 10,000 13,000 19,000 27000
Voltage, Cycle, Phase V/Hz/- 208-230/60/1 208-230/60/1 208-230/60/1 208-230/60/1 208-230/60/1
Airflow (Turbo/H/M/L/Quiet) CFM 353/312/270/230/188 353/312/270/230/188 400/353/282/247/218 540/500/447/365/306 845/670/530/470
Max. Ext. Static Pressure in.W.G (Pa) 0.16 (40) 0.16 (40) 0.16 (40) 0.16 (40) 0.6 (150)
Indoor Sound dB (Turbo/H/M/L/Quiet) 35/33/29/26/21 35/33/29/26/22 38/35/29/26/23 31/29/23/29/25 38/35/32/29
Dimension: HxWxD in (mm) 7 5/16 x 33 7/16 x16 9/16(185x850x420)
7 5/16 x 46 1/16 x16 9/16
(185x1170x420)
9 7/8 x 37 5/8 x 25 3/4
(250x957x655)
Weight (Ship/Net)- lbs (kg) 47.2/36.8 (21.4/16.7) 47.2/36.8 (21.4/16.7) 47.2/36.8 (21.4/16.7) 61.8/48.5(28/22) 68.8/81.1 (31.2/36.8)
Liquid / Suction O.D. in 1/4 3/8 1/4 3/8 1/4 3/8 1/4 1/2 3/8 5/8
Drainpipe Size O.D. in 1 1/4 1 1/4 1 1/4 1 1/4 1 1/4
Condensate Pump Standard Standard Standard Standard Standard
Max. Drain-Lift height in(mm) 27 9/16 (700) 27 9/16 (700) 27 9/16 (700) 27 9/16 (700) 27 9/16 (700)
Cassette Indoor AB09SC2VH* AB12SC2VH* AB18SC2VH* AL24LP2VH*
Rated Cooling Capacity Btu/hr 9,000 12,000 18,000 24200
Rated Heating Capacity Btu/hr 10,000 13,000 19,000 27300
Voltage, Cycle, Phase V/Hz/- 208-230/60/1 208-230/60/1 208-230/60/1 208-230/60/1
Airflow (Turbo/H/M/L/Quiet) CFM
410/365/305/265/205 410/365/305/265/205 470/410/365/295/252 740/630/480/400
Indoor Sound dB (Turbo/H/M/L/Quiet)
42/40/36/32/25 42/40/36/32/25 45/42/40/36/32 38/35/32/29
Grill Model PB-700IB PB-700IB PB-700IB PB-950KB
Chassis Dimension: HxWxD in (mm) 10 1/4 x 22 7/16 x 2 3/8 (260 x 570 x 570) 9 5/8 x 33 1/8 x 33 1/8 (246 x 840 x840)
Grill Dimension: HxWxDin (mm) 2 3/8 x 27 9/16 x 27 9/16 (60 x 700 x 700) 2 x 3 1/8 x 3 1/8 (50 x 950 x 950)
Weight (Ship/Net)- lbs (kg) 46.3/37.5 (21/17) 68.4/79.4 (31/36)
Liquid / Suction O.D. in 1/4 3/8 1/4 3/8 1/4 1/2 3/8 5/8
Drainpipe Size O.D. in 1 1/4 1 1/4 1 1/4 1
Condensate Pump Standard Standard Standard Standard
Max. Drain-Lift height in(mm) 27 9/16 (700) 27 9/16 (700) 27 9/16 (700) 47 1/4(1200)
Model Number Outdoor 2U18MS2VHB 3U24MS2VHB 4U36MS2VHB
Operating Range
Cooling °F(°C) 14~115(-10~46) 14~115(-10~46) 14~115(-10~46)
Heating °F(°C) -4~75(-20~24) -4~75(-20~24) -4~75(-20~24)
Power Supply
Voltage, Cycle, Phase V/Hz/- 208-230/60/1 208-230/60/1 208-230/60/1
Wire Size between ID and OD 14/4 AWG Stranded 14/4 AWG Stranded 14/4 AWG Stranded
Maximum Fuse Size A 25 25 30
Minimum Circuit Amp A 15 18 23
Cooling Non-ducted
Rated Capacity Btu/hr 17,400 22,600 34,000
Capacity Range Btu/hr 4,400-19,400 5,000-24,500 5,000-36,000
Rated Power Input W 1,650 2,250 3,770
SEER 16.0 18.0 18.0
EER 10.5 10.0 9.0
Cooling Ducted
Rated Capacity Btu/hr 15,000 21,000 31,000
Capacity Range Btu/hr 4,400-19,400 5,000-23,000 5,000-34,000
Rated Power Input W 1,760 2,416 3,590
SEER 16.0 16.0 16.0
EER 8.5 8.5 8.5
Heating Non-ducted
Rated Heating Capacity 47°F Btu/hr 19,200 23,000 34,600
Heating Capacity Range Btu/hr 6,100-22,100 6,100-25,500 6,100-36,500
Rated Power Input W 1,570 1,700 2,650
HSPF 9.0 10.0 10.0
Rated Heating Capacity 17°F Btu/hr 13,000 15,000 22,000
Heating Ducted
Rated Heating Capacity 47°F Btu/hr 18,000 22,000 33,000
Heating Capacity Range Btu/hr 6,100-22,100 6,100-25,000 6,100-35,000
Rated Power Input W 1,700 2,100 3,000
HSPF 8.5 8.5 9.0
Rated Heating Capacity 17°F Btu/hr 10,000 14,000 21,000
Outdoor Unit
Compressor Type DC Interver Driven Rotary
Outdoor Fan Speed RPM 300 ~ 900 300 ~ 900 300 ~ 900
Outdoor Noise Level dB 53 54 56
Dimension: Height in (mm) 27 1/16(688) 28 3/4(730) 33 1/16(840)
Dimension: Width in (mm) 31 7/8(810) 33 7/8(860) 37 5/16(948)
Dimension: Depth in (mm) 11 5/16(288) 12 1/8(308) 13 3/8(340)
Weight (Ship/Net)- lbs (kg) 102.5/95.9(46.5/43.5) 123.4/116.8(56/53) 191.8/167.5(87/76)
Connectable Indoor unit quantity 2 2 or 3 2, 3 or 4
Refrigerate Line
Connections Flare Flare Flare
Liquid O.D. in 1/4 1/4 1/4 1/4 1/4 1/4 1/4 1/4 1/4
Suction O.D. in 3/8 3/8 3/8 3/8 3/8 3/8 3/8 3/8 1/2
Factory Charge Oz 49.5 67.0 113.0
Maximum Line Length Ft / m 100/30 200/60 230/70
Maximum Height Ft / m 50/15 50/15 50/15
Maximum Line Length for each individual indoor unit Ft / m 65/25 82/25 82/25
3 4