Installation guide
INSTALLATION
PAGE 10
ENGLISHSECTION A
Step 4 - Charging
See Steps 5.2 - 5.5 for evacuating the system prior to
charging. The standard lineset length is 25ft. If the installation
length is dierent, adjust the refrigerant charge by .2 oz / ft.
for the 9K, 12K, 18K, and 24K model. (Step 4 - Illustration 4)
Please kindly explain to our customers how to operate
through the instruction manual.
This product contains uorinated greenhouse gases covered
by the Kyoto Protocol. Do not vent into the atmosphere.
Refrigerant type: R410A
GWP* value: 1975
GWP = global warming potential
Please ll in with indelible ink,
• 1 the factory refrigerant charge of the product
• 2 the additional refrigerant amount charged in the eld and
• 1+2 the total refrigerant charge on the refrigerant charge
label supplied with the product.
The lled out label must be adhered in the proximity of the
product charging port (e.g. onto the inside of the stop valve
cover).
A - contains uorinated greenhouse gases covered by the
Kyoto Protocol
B - factory refrigerant charge of the product: see unit name
plate
C - additional refrigerant amount charged in the eld
D - total refrigerant charge
E - outdoor unit
F - refrigerant cylinder and manifold for charging
Refrigerant Charge Label
System Test
Check Items for Test Run
1
1+2=
oz
R410A
2
oz
2=
1=
B
C
D
FE
oz
A
Contains fluorinated greenhouse gases
covered by the Kyoto Protocol
Put check mark √ in boxes
No gas leak from linesets?
Are the linesets insulated properly?
Are the connecting wirings of indoor and outdoor rmly
inserted to the terminal block?
Is the connecting wiring of indoor and outdoor rmly
xed?
Is condensate draining correctly?
Is the ground wire securely connected? Is the indoor unit
securely xed?
Is power source voltage correct according to local code?
Is there any noise?
Is the lamp normally lighting?
Are cooling and heating (when in heat pump) performing
normally?
Is the operation of room temperature sensor normal?