Parameter Display Description
Compressor
O Delay
Time
Use the buttons to set
Compressor O Delay Time.
Range 3 to 5 minutes
Default 5 minutes
Increment 1 minute
Heat/Cool
Dierential
Use the buttons to change the
minimum dierential between the heat and
cool setpoints. Press “Fan” to accept.
If this value is changed, the current set
point, schedule set point, min/max setpoint
or freeze protection setpoint may be altered
automatically to accommodate the change.
Range 2°F to 6°F (1°C to 3°C)
Increment 1°F (0.5°C)
Span
(Hysteresis)
Use the buttons to set the
span between the room and set point tem-
peratures. Press “Fan” to accept and go to
the next parameter.
Range 0.5°F to 2°F (0.25°C to 1°C)
Increment 0.5°F (0.25°C)