User Manual
ANALOG CONTROL
131
External control of Shutdown
Background
The output of the power supplies can be
configured to shut down via an external switch.
The voltage across pins 7 and 20 are internally
pulled to +5V ±5% @ 500uA with 10kΩ pull-up
resistor. The output is turned off when a low
TTL level signal is applied.
Connection
PSUSwitch
Analog
connector
20
7
Output
Terminal
2 core shielded
wire or twisted
pair
Pin7→ Switch
Pin20 → Switch
Wire shield → negative (-) output terminal
Steps
1. Connect the external switches according to the
connection diagrams above.
2. The switch will now shut down the power
supply when shorted.