User's Manual
73
LoggerSetup(StandardProfessionalVersion)
TheLoggerSetupwindowmaybedisplayedbyselectingtheappropriatemenuitemorfunctionbuttoninthe
mainwindoworbysimplypressingF4.Itallowsadjustmentofthepropertiesoftheactualselectedlogger:
Loggerno.:Eachloggerhasitsownuniqueloggernumberthatisneededforidentification.Thisnumbercan
befoundontheloggercase.ThenumberhastobeenteredexactlyintotheLoggerno.fieldforeachlogger
oftheproject,otherwisetheloggercannotbefoundbytheCommLink.
Posi
tion:Ashortdescriptionofthepositiontheloggerisdeployed.Somedatashouldbeenteredbymeans
ofeasieridentificationofthelogger.
Comment:Adatafieldprovidedforvarioususerspurposes.Entryisarbitrary.
StartMeas.:Startingtimeofdailymeasurement(defaultvalue:02:00)
Stop.Meas.:Stoptimeofdai
lymeasurement(defaultvalue:04:00)
Interval:Measurementinterval,selectablefrom1secto3min(defaultvalue:3sec)
Restrictions:Whensettingintervalto1secmax.measurementdurationis12hours,otherwiseitcanbeset
tomax.23hours59min.
Noise characteristics is monitored and an
alyzed only between starting and stop time. By restriction of the
measurementtimeitispossibletoexcludedaytimeperiodswithinterferingnoisesources(e.g.traffic)from
beinganalyzed,thusleadingtofalseevaluationresults.
Radiooperationfrom:Startofradiooperationperiod.Duringradiooperationperiod,loggersarereacha
ble
in5speriodsinordertoensureeasyconnectionduringsynchronization.Outsidetheradiooperationperiod,
loggersgotosleepmodeinordertosavebatterycapacity.Insleepmode,loggersarereachablein30second
periods:Theycanbeconnectedtowithin30secondsusingtheloggerst
atefunctionorduringsynchronizing
according to logger list (in case wake up loggers function is activated, see Logger Synchronization).
Synchronizingusing"onlyreachableloggersmode"isnotrecommendedoutsideradiooperationmode.
Radiooperationto:Endofradiooperationperiod
Note:Eventually,theloggerclockshouldbecheckedtoen
sureproperoperationregardingmeasurementand
radiocommunicationsettings.
Copy to all loggers (not available when window invoked by
theInsertloggerfunction):Foreasiersetupitispossibletocopychangesofthemeasurementsettingstoall
loggersoftheproject.
Latitude and longitude coordinates: (see Logger
Map)
Thenavigationbuttonsmaybeusedtoswitchtoanotherloggerwithout
leavingtheLoggerSetupwindow.Anychangestothesettingswon'tbesavedtotheinternaldatabaseunless