User's Manual

57 I 72
the Repeater remains below the limit value entered above. Preset:
6 days
Warning when temp. above maximum for: Enter the number of
days after which a warning is displayed if the temperature
measured at the Repeater remains above the limit value entered
above. Preset: 3 days
Problem when temp. above maximum for: Enter the number of
days after which an error is displayed if the temperature measured
at the Repeater remains above the limit value entered above.
Preset: 6 days
6.1.4 Logger Table
Figure 66: Settings > Logger
Possible leak: Enter the values based on experience for displaying
a possible leak. Preset: 40
Probable leak: Enter the values based on experience for displaying
a probable leak. Preset: 70
Warning when not reachable for: Define the number of days after
which a warning is displayed if a Logger was not reached. Preset:
4 days
Problem when not reachable for: Define the number of days after
which an error is displayed if a Logger was not reached. Preset: 8
days
Warning when below: Enter the charge state of the batteries of the
Loggers below which a warning is displayed. Preset: 2.90 V
Problem when below: Enter the charge state of the batteries of the
Loggers below which an error is displayed. Preset: 1.40 V
Leak Value Warning
Limits
Reachability Warning
Limits
Battery Voltage
Warning Limits