Problem when temp. above maximum for: Enter the number of
days after which an error is displayed if the temperature measured
at the Alpha remains above the limit value entered above. Preset:
4 days
6.1.3 Repeater Table
Figure 65: Settings > Repeater
Warning when not reachable for: Define the number of days after
which a warning is displayed if a Repeater was not reached.
Preset: 3 days
Problem when not reachable for: Define the number of days after
which an error is displayed if a Repeater was not reached. Preset:
6 days
Warning when below: Enter the charge state of the batteries of the
Repeaters below which a warning is displayed. Preset: 2.80 V
Problem when below: Enter the charge state of the batteries of the
Repeaters below which an error is displayed. Preset: 2.60 V
Minimum temperature limit: Enter the lower temperature value
below which a warning or an error is displayed. Preset: -30.0°C
Maximum temperature limit: Enter the upper temperature value
above which a warning or an error is displayed. Preset: 70.0°C
Warning when temp. below minimum for: Enter the number of days
after which a warning is displayed if the temperature measured at
the Repeater remains below the limit value entered above. Preset:
3 days
Problem when temp. below minimum for: Enter the number of days
after which an error is displayed if the temperature measured at
Reachability Warning
Limits
Battery Voltage
Warning Limits
Temperature