User's Manual
55 I 72
6.1.2 Alpha Table
Figure 64: Settings > Alpha
Warning when not reachable for: Define the number of days after
which a warning is displayed if an Alpha was not reached. Preset:
2 days
Problem when not reachable for: Define the number of days after
which an error is displayed if an Alpha was not reached. Preset: 4
days
Warning when below: Enter the charge state of the batteries of the
Alphas below which a warning is displayed. Preset: 6.00 V
Problem when below: Enter the charge state of the batteries of the
Alphas below which an error is displayed. Preset: 5.50 V
Minimum temperature limit:
Enter the lower temperature value below which a warning or an
error is displayed. Preset: -30.0°C
Maximum temperature limit:
Enter the upper temperature value above which a warning or an
error is displayed. Preset: 70.0°C
Warning when temp. below minimum for: Enter the number of days
after which a warning is displayed if the temperature measured at
the Alpha remains below the limit value entered above. Preset: 2
days
Problem when temp. below minimum for: Enter the number of days
after which an error is displayed if the temperature measured at
the Alpha remains below the limit value entered above. Preset: 4
days
Warning when temp. above maximum for: Enter the number of
days after which a warning is displayed if the temperature
measured at the Alpha remains above the limit value entered
above. Preset: 2 days
Reachability Warning
Limits
Battery
Voltage
Warning Limits
Temperature
Warning Limits