Datasheet
Transfer Switches
04/2019
mail@gude.info
www.gude.info
shop.gude.info
GUDE Systems GmbH
Von-der-Wettern-Str. 23
51149 Koeln
•
Germany
T +49.221.912 90 97
F +49.221.912 90 98
Highlights at a glance
Typical transfer time: 7-10 ms
Residual current metering (RCM)
Energy metering
Expert Transfer Switch 8801-1
Automatic transfer switch (ATS) for redundant power supply of network components
Order Code Product Feature Max. Current
8801-1 Expert Transfer Switch 8801-1 ATS, 6 outlets IEC C13, 1 outlet IEC C19, RCM 16 A
7101 Temperature Sensor 7101 Cable sensor with splash-proof sensor head (IP64),RJ45 connector,-20°C to +80°C,cable ca. 2.3 m
7104 * Temperature Sensor 7104 Cable sensor, RJ45 connector, -20°C to +80°C, cable ca. 2.3 m
7105 * Temp., Humidity Sensor 7105 Cable sensor, RJ45 connector, -20°C to +80°C, 0-90% humidity, cable length ca. 2.3 m
7106 * Temp., Humidity, Air pressure
Sensor 7106
Cable sensor, RJ45 connector, 20°C to +80°C, 0-90% humidity, 300-1100 hPa, cable ca. 2.3 m
* Sensors also available with calibrated temperature range: 7104-2, 7105-2, 7106-2
7201 Temperature Sensor 7201 Box case with RJ45 socket, -20°C to +80°C
7202 Temp., Humidity Sensor 7202 Box case with RJ45 socket, -20°C to +80°C, 0-90% humidity
0804 IEC Extension Cable 0804 Extension cable for IEC C13 to C14, length: 3 m
0807 Cable Holder 0807 Cable holder with 13 xation bridges for cable attachement on rear side of device
2
6
Connectors on rear panel
IPv6
HTTPS
SSL
SNMPv3
Telnet
Modbus TCP
Features
• Automatic transfer to alternate power supply if blackout of
primary power supply occurs (A or B)
• Switches also if phase is shifted
• If primary power supply returns (A or B), automatic shift-in
possible
• LED display featuring status of power supply including phase-
shift
• Metering of energy, current, power factor, phase angle,
frequency, voltage and active/apparent/reactive power
• 2 energy meters, one meter continuously, the other resettable
• Metering of residual current type A (RCM)
• Clearly visible LED display for total current, IP address, sensor
data and error reports
• 2 interfaces for optional sensors for environmental monitoring
(temperature, humidity and air pressure)
• Messages by e-mail, Syslog and SNMP traps depending on
threshold values of energy and sensor metering
• Comfortable conguration by web browser, Windows or Linux
tool
• Firmware update via Ethernet during operation
• IPv6-ready
• HTTP/HTTPS, e-mail (SSL, STARTTLS), DHCP, Syslog
• SNMPv1, v2c, v3 (Get/Traps)
• TLS 1.0, 1.1, 1.2
• Radius and Modbus TCP protocol supported
• Configuration and control over Telnet
• Access control via IP Access Control List
• Low power consumption
• Developed and manufactured in Germany
Electrical Connections
• 2 power supplies IEC C20, max. 16 A
• 6 load outlets IEC C13, max. 10 A
• Load outlet IEC C19, max. 16 A
• Ethernet connector RJ45 (10/100 Mbit/s)
• Galvanic isolated signal output (Sub-D 9-pin)
• 2 sensor interfaces (RJ45) for optional sensors
Technical Details
• 19 inch, 1 rack unit
• Dimensions of device:
LxHxD: 43.9 x 4.4 x 19.5 cm
(without brackets)
• Weight: ca. 2.5 kg
• Operating temperature:
0 - 50 °C
• Storage temperature: -20 - 70 °C
• Relative humidity: 0 - 95 % (non-condensing environment)