Datasheet

Transfer Switches
04/2019
mail@gude.info
www.gude.info
shop.gude.info
GUDE Systems GmbH
Von-der-Wettern-Str. 23
51149 Koeln
Germany
T +49.221.912 90 97
F +49.221.912 90 98
Highlights at a glance
Typical transfer time: 7-10 ms
Residual current metering (RCM)
Energy metering
Expert Transfer Switch 8801-1
Automatic transfer switch (ATS) for redundant power supply of network components
Order Code Product Feature Max. Current
8801-1 Expert Transfer Switch 8801-1 ATS, 6 outlets IEC C13, 1 outlet IEC C19, RCM 16 A
7101 Temperature Sensor 7101 Cable sensor with splash-proof sensor head (IP64),RJ45 connector,-20°C to +80°C,cable ca. 2.3 m
7104 * Temperature Sensor 7104 Cable sensor, RJ45 connector, -20°C to +80°C, cable ca. 2.3 m
7105 * Temp., Humidity Sensor 7105 Cable sensor, RJ45 connector, -20°C to +80°C, 0-90% humidity, cable length ca. 2.3 m
7106 * Temp., Humidity, Air pressure
Sensor 7106
Cable sensor, RJ45 connector, 20°C to +80°C, 0-90% humidity, 300-1100 hPa, cable ca. 2.3 m
* Sensors also available with calibrated temperature range: 7104-2, 7105-2, 7106-2
7201 Temperature Sensor 7201 Box case with RJ45 socket, -20°C to +80°C
7202 Temp., Humidity Sensor 7202 Box case with RJ45 socket, -20°C to +80°C, 0-90% humidity
0804 IEC Extension Cable 0804 Extension cable for IEC C13 to C14, length: 3 m
0807 Cable Holder 0807 Cable holder with 13 xation bridges for cable attachement on rear side of device
2
6
Connectors on rear panel
IPv6
HTTPS
SSL
SNMPv3
Telnet
Modbus TCP
Features
Automatic transfer to alternate power supply if blackout of
primary power supply occurs (A or B)
Switches also if phase is shifted
If primary power supply returns (A or B), automatic shift-in
possible
LED display featuring status of power supply including phase-
shift
Metering of energy, current, power factor, phase angle,
frequency, voltage and active/apparent/reactive power
2 energy meters, one meter continuously, the other resettable
Metering of residual current type A (RCM)
Clearly visible LED display for total current, IP address, sensor
data and error reports
2 interfaces for optional sensors for environmental monitoring
(temperature, humidity and air pressure)
Messages by e-mail, Syslog and SNMP traps depending on
threshold values of energy and sensor metering
Comfortable conguration by web browser, Windows or Linux
tool
Firmware update via Ethernet during operation
IPv6-ready
HTTP/HTTPS, e-mail (SSL, STARTTLS), DHCP, Syslog
SNMPv1, v2c, v3 (Get/Traps)
TLS 1.0, 1.1, 1.2
Radius and Modbus TCP protocol supported
Configuration and control over Telnet
Access control via IP Access Control List
Low power consumption
Developed and manufactured in Germany
Electrical Connections
2 power supplies IEC C20, max. 16 A
6 load outlets IEC C13, max. 10 A
Load outlet IEC C19, max. 16 A
Ethernet connector RJ45 (10/100 Mbit/s)
Galvanic isolated signal output (Sub-D 9-pin)
2 sensor interfaces (RJ45) for optional sensors
Technical Details
19 inch, 1 rack unit
Dimensions of device:
LxHxD: 43.9 x 4.4 x 19.5 cm
(without brackets)
Weight: ca. 2.5 kg
Operating temperature:
0 - 50 °C
Storage temperature: -20 - 70 °C
Relative humidity: 0 - 95 % (non-condensing environment)

Summary of content (1 pages)