Datasheet
Transfer Switches
04/2019
mail@gude.info
www.gude.info
shop.gude.info
GUDE Systems GmbH
Von-der-Wettern-Str. 23
51149 Koeln
•
Germany
T +49.221.912 90 97
F +49.221.912 90 98
Expert Bypass Switch 8701 Series
Mechanical bypass switch for uninterrupted replacement of UPS systems
6
Power connectors on rear panel of Expert Bypass Switch 8701-2
Power connectors on rear panel of Expert Bypass Switch 8701-2
Order code Product Feature Maximum Current
8701-1 Expert Bypass Switch 8701-1 Bypass switch, 6 load outlets IEC C13, load outlet IEC C19,
10 A fuse for IEC C19 load outlet
10 A
8701-2 Expert Bypass Switch 8701-2 Bypass switch, 6 load outlets IEC C13, 1 load outlet IEC C19 16 A
0804 IEC Extension Cable 0804 Extension cable for IEC C13 to C14, length: 3 m
0807 Cable Holder 0807 Cable holder with 13 xation bridges for cable attachement on rear side of device
Features
• Uninterrupted replacement or maintenance of UPS systems
through bypass switch without shutdown of connected loads
• Available in two versions for 10 A or 16 A current
(8701-1 or 8701-2)
• 6 load outlets IEC C13, 10 A
• 1 load outlet IEC C19, 16 A
• 10 A fuse for protection of IEC C19 outlet (8701-1)
• Easily operable selection switch
• Switch position „Netz“: Connected loads are operated directly
with mains voltage
• Switch position „USV“: Connected loads are operated with UPS
system voltage
• Clearly visible LED display for switch status
• Low internal power consumption
• Developed and manufactured in Germany
Electrical Connections
Expert Bypass Switch 8701-1 / 8701-2
• Power supply „von Netz“ IEC C14, 10 A / IEC C20, 16 A
• Output „zur USV“ IEC C13, 10 A / IEC C19, 16 A
• Input „von USV“ IEC C14, 10 A / IEC C20, 16 A
• 6 load outlets IEC C13, 10 A
• Load outlet IEC C19, 16 A
Technical Details
• 19 inch, 1 rack unit
• Dimensions of device: LxHxD: 43.4 x 4.4 x 16.5 cm
(without brackets)
• Weight: ca. 2.2 kg
• Operating temperature: 0-50 °C
• Storage temperature: -20 - 70 °C
• Relative humidity: 0 - 95 % (non-condensing environment)