Datasheet
Switched & Metered Power Distribution Units
12/2019
mail@gude.info
www.gude.info
shop.gude.info
Gude Analog- und Digitalsysteme GmbH
Eintrachtstr. 113
50668 Koeln
•
Germany
T
+49.221.912 90 97
F +49.221.912 90 98
Order Code Product Rear connectors Shared Features
8025-1 Expert Power Control 8025-1 4 x IEC C13 Operating voltage: 230 V , max.: 16 A
Energy metering per power port
Residual current metering type A
Overvoltage protection (SPD) type 3
2 sensor ports with RJ45 socket
HTTPS, SSL, IPv6, SNMPv3, Telnet, Radius, Modbus TCP
8035-1 Expert Power Control 8035-1 8 x IEC C13
8035-2 Expert Power Control 8035-2 8 x IEC C13 Lock
8045-1 Expert Power Control 8045-1 8 x safety socket type F (DE)
8045-2 Expert Power Control 8045-2 12 x IEC C13
Order Code Product Feature
7101 Temperature Sensor 7101 Cable sensor with splash-proof sensor head (IP64), RJ45 connector, -20°C to +80°C,
cable ca. 2.3 m
7104 * Temperature Sensor 7104 Cable sensor, RJ45 connector, -20°C to +80°C, cable ca. 2.3 m
7105 * Temp./Humidity Sensor 7105 Cable sensor, RJ45 connector, -20°C to +80°C, 0-90% humidity, cable ca. 2.3 m
7106 * Temp./Humidity/Air pressure
Sensor 7106
Cable sensor, RJ45 connector, 20°C to +80°C, 0-90% humidity, 300-1100 hPa,
cable ca. 2.3 m
* Sensors also available with calibrated temperature range: 7104-2, 7105-2, 7106-2
0804 IEC Extension Cable 0804 Extension cable for IEC C13 to C14, length: 3 m
0871 Desk/Wall Bracket 0871 Accessories for mounting a 19-inch device under a tabletop or on a wall
0872 Cable Holder 0872 13 fi xation bridges for load cables at the rear side (not for 8031-3)
Electrical Connections
• Power supply IEC C20, max. 16 A, 230 V
• Power Ports: 4, 8 or 12 IEC C13 (Lock), max. 10 A
• Ethernet connector RJ45 (10/100 Mbit/s)
• Serial interface RS232 (Sub-D 9-pin)
• 2 RJ45 interfaces for optional sensors
Technical Details
• Dimensions: 19 inch, 1 rack unit
• LxHxD: 43.9 x 4.4 x 17.8 cm (without brackets)
• Weight: ca. 2.2 kg
• Operating temperature: 0-50 °C
• Storage temperature: -20 - 70 °C
• Relative humidity: 0 - 95 % (non-condensing environment)
Residual current metering
Overvoltage protection type 3
4-, 8- or 12-fold switched PDU with energy monitoring per power port
Features
• Up to 12 Power Ports individually switchable directly on the
device, via HTTPS, SNMP, command line tool and RS232 serial
interface
• Status and Power-up delay (0...9999 seconds) adjustable
individually for each Power Port after power blackout
• Latency time of 1 second prevents simultaneous power-up of
multiple Power Ports
• Programmable timetables and turn-on/turn-o sequences
• 2 energy meters per port (outlet-metered): one meter continu-
ously, the other resettable
• Metering of energy, current, power factor, phase angle,
frequency, voltage and active / apparent / reactive power
• Residual current metering type A
• A clearly visible LED display for total current, IP address,
sensor data and error reports
• An individual watchdog (ICMP/TCP) can be assigned for
each Power Port
• Integrated overvoltage protection (SPD) type 3 prevents
damage of device and of connected consumers (L-N, L/N-PE),
status retrievable over network
• 2 interfaces for optional sensors for environmental monitoring
(temperature, humidity and air pressure)
• Event-based port switching possible by set sensor thresholds
• Internal beeper for acoustic alarm for set sensor thresholds
• Comfortable confi guration by web browser, Windows or Linux
tool
• Firmware update via Ethernet during operation
• IPv6-ready
• HTTP/HTTPS, e-mail (SSL, STARTTLS), DHCP, Syslog
• SNMPv1, v2c, v3 (Get/Traps)
• TLS 1.0, 1.1, 1.2
• Radius and Modbus TCP support
• Confi guration and control via Telnet
• Access control via IP Access Control List
• Android and iOS app Gude Control allows access from anywhere
• Low internal power consumption
• Developed and manufactured in Germany
4, 8, 12
2
8