Specification
4 of 5
®
*Function of Evolution Controller
† Can be set to weekly or monthly
Model
G007033-0 (11kW)
No. of Poles 2
Current Rating (Amps) 200
Voltage Rating (VAC) 120/240, 1Ø
Utility Voltage Monitor (Fixed)*
-Pick-up
-Dropout
80%
65%
Return to Utility* approx. 13 sec
Exercises bi-weekly for 12 minutes*† Standard
UL Listed Standard
Enclosure Type NEMA/UL 3R
Circuit Breaker Protected 22,000
Lug Range 250 MCM - #6
H2
DEPTH
H1
W2
W1
*Function of Evolution Controller
† Can be set to weekly or monthly
Model
G007030-0 (9kW) G007032-0 (11kW)
No. of Poles 2 2
Current Rating (Amps) 100 100
Voltage Rating (VAC) 120/240, 1Ø 120/240, 1Ø
Utility Voltage Monitor (Fixed)*
-Pick-up
-Dropout
80%
65%
80%
65%
Return to Utility* approx. 15 sec approx. 15 sec
Exercises bi-weekly for 12 minutes*† Standard Standard
UL Listed Standard Standard
Total Circuits Available 16 16
Tandem Breaker Capabilities 8 Tandems 8 Tandems
Circuit Breaker Protected
Available RMS Symmetrical
Fault Current @ 250 Volts
10,000 10,000
H2
DEPTH
H1
W2
W1
9/11 kW
switch options
9/11 kW
Limited Circuits Switch Features
16 circuits.
Rated for all classes of load, 100% equipment rated, both inductive and
resistive.
2 pole, 250 VAC contactors.
30 millisecond transfer time.
Single coil design.
Main contacts are silver plated or silver alloy to resist welding and sticking.
NEMA/UL 3R aluminum outdoor enclosure.
Multi listed for use with 1" standard, tandem, GFCI and AFCI breakers
from Siemens, Murray, Eaton and Square D for the most flexible and cost
effective install.
Dimensions
Height Width
Depth
H1 H2 W1 W2
in 26.75 30.1 10.5 13.5 6.91
mm 679.4 764.3 266.7 343.0 175.4
Wire Ranges
Conductor Lug Neutral Lug Ground Lug
1/0 - #14 2/0 - #14 2/0 - #14
Limited Circuits Switch Features
16 circuits, breakers not included.
Rated for all classes of load, 100% equipment rated, both inductive and
resistive.
2 pole, 250 VAC contactors.
30 millisecond transfer time.
Single coil design.
Main contacts are silver plated or silver alloy to resist welding and sticking.
NEMA/UL 3R aluminum outdoor enclosure.
Multi listed for use with 1" standard, tandem, GFCI and AFCI breakers
from Siemens, Murray, Eaton and Square D for the most flexible and cost
effective install.
Dimensions
Service Rated Smart Switch Features
available on 11 kW model only
Includes Digital Power Management Technology standard (DPM).
Intelligently manages up to four air conditioner loads with no additional
hardware.
Up to eight more large (240 VAC) loads can be managed when used in
conjunction with Smart Management Modules (SMMs).
Electrically operated, mechanically-held contacts for fast, clean connec-
tions.
Rated for all classes of load, 100% equipment rated, both inductive and
resistive.
Service equipment rated, dual coil design.
Rated for both aluminum and copper conductors.
Main contacts are silver plated or silver alloy to resist welding and sticking.
NEMA/UL 3R aluminum outdoor enclosure.
200 Amps 120/240, 1ø
Open Transition Service Rated
Height Width
Depth
H1 H2 W1 W2
in 26.75 30.1 10.5 13.5 6.91
mm 679.4 764.3 266.7 343.0 175.4