- Guardian Technologies, LLC Liquid Cooled Gas Engine Generator Sets Specification Sheet
  COMMERCIAL 100 kW 
KW RATING  100
ENGINE SIZE  6.8 Liter V-10
GENERATOR OUTPUT VOLTAGE/KW - 60Hz  KW  AMP  CB Size
  120/240V, single phase, 1.0 pf  100 LP / 98 NG  416.6 LP / 408.3 NG  450
  120/208V, 3-phase, 0.8 pf  100 LP / 98 NG  347.4 LP / 340.4 NG  400
  120/240V, 3-phase, 0.8 pf  100 LP / 98 NG  301 LP / 295 NG  350
  277/480V, 3-phase, 0.8 pf  100 LP / 98 NG  150.5 LP / 147.5 NG  175
GENERATOR LOCKED ROTOR KVA
 AVAILABLE @ VOLTAGE DIP OF 35%
  Single phase or 208V & 240V 3-phase    190
 480V 3-phase    225
ENGINE FUEL CONSUMPTION 
(Natural Gas) (Propane)    Natural Gas  Propane 
     (ft
3
/hr.) (gal/hr.) cu ft/hr
 Exercise cycle    130  1.42  52.3 
  25% of rated load    371  4.06  149.4
  50% of rated load    713  7.81  287.4
  75% of rated load    994  10.88  400.4
  100% of rated load    1260  13.80  507.8
ENGINE COOLING
 Air flow 
(inlet air including alternator and combustion air) ft
3
/min 5,500
  System coolant capacity  US gal.  4.5
  Heat rejection to coolant   BTU/hr.  342,000
  Max. operating air temp. on radiator  °C (°F)  60 (150)
  Max. ambient temperature  °C (°F)  50 (140)
COMBUSTION AIR REQUIREMENTS
  Flow at rated power 60 Hz  cfm  262
SOUND EMISSIONS IN DBA
  db(A) @ 23 feet in exercise mode    61 
  db(A) @ 23 feet at normal operating load    72 
EXHAUST
  Exhaust flow at rated output 60 Hz  cfm 888 
  Exhaust temp. at muffler outlet  °F  960 
ENGINE PARAMETERS
  Rated synchronous RPM  60 Hz  2300
  HP at rated KW  60 Hz  168
POWER ADJUSTMENT FOR AMBIENT CONDITIONS
 Temperature Deration
    3% for every 10 °C above - °C  25 
    1.65% for every 10 °F above - °F  77
 Altitude Deration 
    1% for every 100 m above - m  183   
    3% for every 1000 ft. above - ft.  600
OPERATING DATA
COMMERCIAL 100 kW
RATING: All three phases units are rated at 0.8 power factor. All single phase units are rated at 1.0 power factor. STANDBY RATING: Standby ratings apply to installations served by a reliable utility 
source. The standby rating is applicable to varying loads for the duration of a power outage. There is no overload capability for this rating. Ratings are in accordance with ISO-3046-1. Design and 
specifications are subject to change without notice. Maximum wattage and current are subject to and limited by such factors as fuel Btu content, ambient temperature, altitude, engine power 
and condition, etc.