Features Q.E.D. programming for quick enrollment of devices. 2-Partitioned Security System VISTA-40 This Control Supports the Ademco 2-Way Voice Interface Module (VIM) For Audio Alarm Verification (AAV) Installation Instructions • Installation Instructions • Installation Instructions N7001–INSTV2 6/97, Part of N7001V2 downloaded from: http://www.guardianalarms.
RECOMMENDATIONS FOR PROPER PROTECTION The Following Recommendations For The Location Of Fire And Burglary Detection Devices Help Provide Proper Coverage For The Protected Premises. Recommendations For Smoke And Heat Detectors With regard to the number and placement of smoke/heat detectors, we subscribe to the recommendations contained in the National Fire Protection Association's (NFPA) Standard #72 noted below.
TABLE OF CONTENTS PART 1. INSTALLATION INSTRUCTIONS ............................................................................. 6 Use Part 1 when installing the hardware components of the installation. Section 1. GENERAL INFORMATION.................................................................................7 SUMMARY OF SYSTEM FEATURES........................................................................7 INTRODUCTION TO THE PARTITIONED SYSTEM ....................................................
Section 6. RELAY OUTPUTS & POWERLINE CARRIER DEVICES.............................31 General Information................................................................................................31 4204 Relay Module................................................................................................31 4300 Transformer & X-10 Devices...........................................................................31 Section 7. THE 4285 PHONE MODULE....................................................
VIM Voice Interface Module Prompts.......................................................................64 Relay Programming................................................................................................65 Zone List Programming ..........................................................................................68 Programming Relays for Silencing of External Sounders When Using the VIM ...........68 Programming the VIM for Relay Triggering on Supervision Fault.........................
PART 1 INSTALLATION INSTRUCTIONS Ð6Ð
Section 1. GENERAL INFORMATION SUMMARY OF SYSTEM FEATURES The VISTA-40 Control is a microprocessor based, programmable, partitioned system, and features EEROM memory technology (power loss does not result in the loss of programmed data).
Descriptors ¥ All programmed descriptors can be displayed (one at a time) by pressing and holding the READY key for 5 seconds, then releasing the key. This serves as a check for installers to be sure all descriptors are entered properly. Event Logging ¥ Event Logging feature keeps record of up to 100 events. Access Control ¥ Provides user-activated access control command which pulses a relay output for controlled opening of access doors (e.g. lobby door).
INTRODUCTION TO THE PARTITIONED SYSTEM Basic Partitioning Features The following lists the partitioning features of the VISTA-40 system. Simple, Secure, Reliable restrictions). Enough to handle the largest ¥ Easy to use and program as the simplest alarm commercial jobs system. ¥ Integrity of security is not compromised for any users ¥ Multiple levels of authority per partition (allows key of the system.
Section 2. INSTALLING THE CONTROL MOUNTING THE CABINET General The VISTA-40 is supplied with a 12.5"W x 14.5"H x 3"D cabinet suitable for use in residential and non-certified commercial burglary installations. Mount the Control cabinet to a sturdy wall using fasteners or anchors (not supplied) in a clean, dry area which is not readily accessible to the general public. The back of the Control cabinet has 4 holes for this purpose.
PHONE LINE CONNECTIONS Standard Phone Line Connections IMPORTANT!: If using a 4285 Phone Module, phone connections must be made exactly as shown in the PHONE MODULE section, even if the system is not programmed to communicate with a monitoring station. The 4285 Phone Module will not function unless the system is wired exactly as described.
Section 3. POWERING THE SYSTEM Primary Power Power to the Control panel is supplied by model No. 1361* Plug-in Transformer which is rated at 16.5VAC, 40VA. Caution must be taken when wiring this transformer to the panel to guard against blowing the fuse inside the transformer (non-replaceable). * NOTE: Use 1361CN Transformer in Canadian installations. Back-Up Power In the event of an AC power loss, the Control panel is supported by a back-up, rechargeable gel cell battery.
Power-Up Procedure 1. Fill out the Polling Loop Current Draw and Auxiliary Device Current Draw Worksheets shown below. Make sure that the currents drawn from these outputs do not exceed their respective ratings. CAUTION: Failure to observe the polling loop current rating will cause a polling loop malfunction. Failure to observe the auxiliary output current rating will result in a battery which does not charge properly, or possibly a tripped circuit breaker. 2.
Section 4. INSTALLING REMOTE KEYPADS General The Control supplies up to 750 mA of auxiliary power for remote keypads, polling loop devices and/or other auxiliary devices such as motion detectors or 4-wire smoke detectors*. The Control supports, independent of auxiliary power considerations, up to 16 addressable remote keypads (6128, 6137, 6139, 6139AV ). Note that since the maximum number of addressable devices connected to the keypad lines is 16, usage of non-keypad devices (ex.
Wire Gauge Setting the Keypad Address NOTE: The length of all wire runs combined must not exceed 2000 feet when unshielded quad conductor cable is used (1000 feet if shielded cable is used.) If more than one keypad is wired to a run, then the above maximum lengths must be divided by the number of keypads on the run (i.e. the maximum length would be 225 feet if two keypads are wired on a #22 gauge run).
6139AV 2-Way Voice Keypads The control supports the VIM Voice Interface Module, which can support up to six 6139AV 2-way voice keypads. These keypads feature a built-in microphone and speaker that allows a central station operator to "listen-in" and/or speak to persons at the protected premises after an alarm has occurred. Note that during this Òlisten-inÓ and/or ÒspeakÓ period, all alarms will be temporarily silenced.
Section 5. ZONE CONFIGURATIONS BASIC 9 HARD-WIRED ZONES General Information Zones 1-9 are reserved for traditional hard-wired devices. The following table summarizes zone usage. Zone 1 Zones 2, 3, 4, 6 Zone 5 Zone 7 Zone 8 Zone 9 EOLR supervised or closed circuit unsupervised devices. Also supports up to sixteen (16) 2-wire smoke detectors. EOLR supervised or closed circuit unsupervised devices. Also supports 4-wire smoke detectors. EOLR supervised or closed circuit unsupervised devices.
Compatible Smoke Detectors Photoelectric Photoelectric w/ 135° heat Photoelectric w/heat sensor, direct wire Photoelectric, direct wire Photoelectric w/heat sensor, direct wire Photoelectric w/B401B base Photoelectric w/heat sensor & B401B base Ionization Ionization, direct wire Ionization w/B401B base Photoelectric duct detector w/DH400 base Ionization duct detect.
Compatible Glass Break Detectors Use detectors which are compatible with the following ratings: Standby Voltage:..........5VDC-Ð13.8VDC Standby Resistance: Greater than 20k ohms (equivalent resistance of all detectors in parallel) Alarm Resistance:.........Less than 1.1k ohms (see note below) Alarm Current: ..............2 mA -Ð10 mA Reset Time:..................Less than 6 seconds The IEI 735L series detectors have been tested and found to be compatible with these ratings.
2-WIRE POLLING LOOP EXPANSION (Zones 10 through 64) General Information The following table summarizes polling loop expansion characteristics. Applications RPM Address (ID) Connections ¥ Built-in 2- wire polling loop interface allows the number of zones to be expanded from the basic 9 zones to up to 64 zones using various Remote Point Modules (RPMs). See ADVISORIES below. ¥ The polling loop provides power to sensors and serves as communication path between the panel and sensors.
Important! Fault Annunciation Compatible Polling Loop Devices Since the phone module, RF receiver(s), VIM and the polling loop are shared among the 2 partitions, the scheme for annunciating their failure follows: Respective faults (for zones 87, 88Ð91, 93 & 97) will report as trouble conditions only, and as such, should be assigned either zone type 00 if no annunciation is desired, or zone type 05 if annunciation as trouble condition is desired.
WIRELESS EXPANSION (Zones 1Ð63) General Information 4281 Series Receivers 4281H 4281M 4281L 5700 Series Transmitters 63 + 1 RF keypad 8 4 5881 Series Receivers 5881H 5881M 5881L 5800 Series Transmitters 63 + 1 RF keypad 16 8 Transmitters Supported By Various Receivers The following table summarizes wireless expansion characteristics. Zones Supported ¥ The system supports up to 63 wireless transmitters (5700 or 5800 series), plus a wireless keypad (5827/5827BD).
The following table highlights the features of each receiver. Feature 4281 series 5881 series Wiring Connects to keypad lines Connects to keypad lines House ID Programmed via #93 Menu Mode. Programmed via #93 Menu Mode (needed only if RF keypad used). Receiver Address Set via DIP switches. Enabled via #93 Device Programming. Set via DIP switches. Enabled via #93 Device Programming. Cover Removal Does not cause alarm or trouble. Does not cause alarm or trouble.
Transmitters The following table summarizes wireless transmitter characteristics. Transmitters (General) NOTE: After replacing a low or dead battery, activate the transmitter and enter the security code + OFF to clear its memory of the "Low Battery" signal. ¥ Supports 5700 or 5800 series transmitters. ¥ Each transmitter has a unique transmitter ID number (Zone #). 5700 series transmitters use DIP switches to set the ID.
Arming/Disarming With RF Keys (5801, 5802, etc.) If Using a 5827BD/5800TM Wireless Keypad and Transmitter Module Wireless Zone Types 5800 series RF keys can be used to arm and disarm the system. These transmitters include the 5801, 5802, 5804 and any other 5800 series transmitter (except 5827 wireless keypad) if programmed for one of zone type responses 20-22. These transmitters are tied to a user in order to provide a record of who armed or disarmed the system.
Fault Annunciation Important Battery Notice Compatible 5700 Series Wireless Devices Since the phone module, RF receiver(s), VIM and the polling loop are shared among the 2 partitions, the scheme for annunciating their failure follows: Respective faults (for zones 87, 88Ð91, 93 & 97) will report as trouble conditions only, and as such, should be assigned either zone type 00 if no annunciation is desired, or zone type 05 if annunciation as trouble condition is desired.
Compatible 5800 Series Wireless Devices (Refer to the installation instructions provided with each transmitter) 5801...................4-Button Transmitter 5802...................Pendant Panic Transmitter 5802CP ..............Belt Clip Panic Transmitter 5802MN..............Belt Clip or Pendant Panic Transmitter 5804...................4-Button transmitter 5806...................Photoelectric Smoke Detector 5807...................Photoelectric Smoke Detector 5808...................
Outputs 2 & 4: Operate, by default, as Fire and Silent Panic/Duress triggers respectively. These triggers may optionally be programmed to act as Arm and Ready status indicators when it is desired to use the 4146 keyswitch. Output 2, 3, & 4 Rating: When Activated: 10Ð13.8 VDC through 5K ohms (2mA max). When De-activated: 1k ohms to ground. Ground Start Module Not intended for use in UL Listed applications.
A momentary short across this zone will arm the system in the "AWAY" mode. If the short is held for more than 3 seconds, the system will arm in the "STAY" mode. After the system has been armed, the next time zone 7 is shorted, the system will disarm. An optional closed-circuit tamper switch (model 112) can be wired in series with zone 7, so that, if the switchplate is removed from the wall, the tamper will open, disabling keyswitch operation until the system is next disarmed from the keypad.
Remote Keypad Sounder Operation & Wiring An optional Amseco PAL 328N can be used for installations where it is desired to remote the sounds produced by the keypad's built-in piezo sounder for one partition. The panel will remote all sounds (i.e. alarm, trouble, chime, entry/exit, etc.) produced by the keypad's built-in sounder except for the short clicks associated with keypad key depression.
Section 6. RELAY OUTPUTS & POWERLINE CARRIER DEVICES General Information The VISTA-40 supports up to 8 relay outputs. These outputs may consist of relay outputs from the 4204 output relay module (4 relay outputs per module) or X-10 device outputs. Outputs can be activated and deactivated by predetermined events such as turning on lights in the event of an alarm condition and/or closing a fire door in the event of a fire alarm condition. Refer to ÒRelay ProgrammingÓ in Section 4 of PART 2.
Section 7. THE 4285 PHONE MODULE General Information The 4285 Phone Module is an add-on accessory for the VISTA-40 that will permit access to the security system via a Touch-tone phone (either on premises or by a call-in when away). Only one Phone Module can be used in this security system and it must be assigned as device address 04 only and assigned to partition 1 using #93 Menu Mode, Device Programming.
Wiring Connections General Wiring The 4285 is wired between the control panel and the premises handset(s). It listens for touch tones on the phone line and reports them to the control panel. During on-premises phone access, it powers the premises phones; during offpremises phone access, it seizes the line from the premises phones and any answering machines. 1.
Zone descriptors must also be programmed, regardless of the type of keypads in use. If this is not done, the Phone Module will be unable to annunciate a description of the zone(s) in alarm, trouble, etc. (the Phone Module will annunciate zone numbers only). In addition, relay voice descriptors can be programmed if output relays are being used. Incoming Handset Telco Line TERMINALS ON CONTROL Æ 26 27 28 TO EARTH GROUND (COLD WATER PIPE, ETC.
Section 8. 2-WAY VOICE KEYPADS & AUDIO ALARM VERIFICATION (AAV) General Information IMPORTANT: Audio alarm verification reports only on the primary phone number. The VISTA-40 features 2-way voice capability when used with the Ademco Voice Interface Module (VIM) and 6139AV 2-way voice keypads.
2. Connect 3 wires from terminals 1, 2, and 3 on the right side of the VIM module to the control, as follows: a. Terminal 1 to the ground terminal (30) on the control. b. Terminals 2 and 3 to the ÒhandsetÓ terminals (26 & 27) on the control. 6139AV Audio Connections To The VIM Module Each 6139AV 2-way Keypad requires a shielded 2-wire connection to the VIM Module.
¥ Chime option for other partition during 2-way voice session. ¥ VIM text option for displaying voice mode text at the keypad. ¥ VIM AC loss option, when enabled, allows 2-way voice communication after AC loss (recommended for installations where someone is on a life support device) ¥ The AUTO CALLBACK option, when enabled, allows callback to initiate 2-way voice communication, otherwise Òlisten in to followÓ (event code 606) is sent at end of alarm report.
Using A Non-Ademco Audio Alarm Verification (AAV) Unit If you prefer to use another manufacturerÕs AAV unit in place of the Ademco VIM unit, contact the manufacturer for information regarding the wiring of their unit to the VISTA-40. When using another manufacturerÕs AAV unit, see Notes below. Some AAV modules allow remote triggering by ring detection at the alarm installation. Please be advised that if this option is selected, it may defeat modem download and 4285 phone module remote access capability.
Section 9. EXTERNAL SOUNDERS Relay Output The Control provides a wet bell relay output which is used to power external alarm sounders. Connections are made to terminals 4 (positive output) and 5 (negative return). See SUMMARY OF CONNECTIONS Diagram. UL Household Installations For installations which must provide UL Listed protection, the total current drawn from this output and the auxiliary power output, combined, must not exceed 750mA in order to comply with the battery independence requirements.
PART 2 PROGRAMMING PROCEDURES Ð 40 Ð
Section 1. GENERAL PROGRAMMING PROCEDURES GENERAL INFORMATION Review the global and specific partitioning features listed in the GENERAL INFORMATION section of the Installation Instructions before programming the system. The system is shipped with a set of pre-programmed default values that are designed to meet the needs of many installations. These can be changed by the installer to suit specific needs if desired, by using a 6139 (AV) alpha keypad*.
Programming Steps IMPORTANT: The programming scheme is different than other Ademco controls and from previous versions of the VISTA-40. Be sure to review these steps before attempting to program this system. 1. 2. 3. Set the keypads to the appropriate addresses. Set factory defaults by pressing *97. This will automatically enable keypad addresses 00-03, so be sure at least one keypad is set to one of these addresses.
Section 2. ZONE TYPES Zone Types & Applicable Sensors The VISTA-40 supports up to 64 zones of hard-wire, polling loop and/or wireless protection, distributed among up to 2 partitions.
Type 05 Trouble by Day/Alarm by Night. This zone type will give an instant alarm if faulted when armed in the Away, Stay, Instant or Maximum (night) modes. During the disarmed state (day), the system will provide a latched trouble sounding from the keypad (and a central station report, if desired). This zone type is usually assigned to a zone which contains a foil-protected door or window (such as in a store), or to a zone covering a "sensitive" area such as a stock room, drug supply room, etc.
Section 3. DATA FIELD PROGRAMMING PROGRAMMING SYSTEM-WIDE (GLOBAL) DATA FIELDS General Procedure The global (i.e. non partition-specific) programming fields are grouped into three sets (referred to as "pages"), as represented in the diagram below. The first page of fields is accessed automatically after entering a field number. To access the other pages of fields (indicated on the programming form by a "1" or "2" in front of the 2-digit field address), press *94.
INDEX TO PROGRAMMING FIELDS In the following pages, the programming fields have been arranged by functional group. Use this index to cross reference the numerical ordered fields on the programming form with the text.
DATA FIELD DESCRIPTIONS The following section arranges the global (system wide) program fields into the following functional groups: Control Options Downloading Options Dialer Options Wireless Options Partitioning Options Event Logging Options Note that zone response types can be programmed in fields *02-*05 & 1*01-1*09, but it is recommended that they be programmed via the #93 Menu Mode. For this reason, these fields are not discussed in this section.
Control Options (continued) *27 Test Report Interval Enter the test reporting interval in hours, 001-199. Enter 000 if no test reporting is desired. If a test report is desired, enter a test code in fields *81 & *82, location 7. Max. 024 for UL. *28 Power Up In Previous State Enter 1 if it is desired that upon power-up, the system will assume the system status prior to power down. Enter 0 if it is desired that the system will always power up in a disarmed state.
Downloader Options *35 Download Phone No. This field is applicable only if downloading will be utilized. Enter the downloading phone number, up to 12 digits (0-9), or #11 (*), #12 (#), #13 (Pause). Do not fill unused spaces. *36 Download ID No. Enter 00Ð09; A-F (10Ð15). Only applicable if downloading will be utilized.
Dialer Options (continued) *43 Dial Tone Detection Determines whether the control will wait for a true dial tone before dialing, or if it will wait for a predetermined delay before dialing (delay is programmed in Dial Tone Pause field *42). The latter may be necessary in high-noise environment Telco networks where noise can be confused with dial tone, resulting in premature dialing. Enter 1 for true dial tone wait. If no dial tone is detected, will dial at end of pause programmed in field *42.
Dialer Options (continued) *80 Zone Type Restores For Types 9-10 *81-*82 *89 Non-Alarm Report Codes Restore Report Timing Enter 1 to enable restore reporting for individual zone types. Enter 0 if no restore report is desired for a zone type. Enter the appropriate report codes as indicated on the programming form. Enter 0 for instant restore report, as zone restores. Enter 1 for reporting after bell timeout if zone restored.
Wireless Options (cont.) 1 * 5 7 Enable 5800 RF Button Global Arm Enter 1 to have the system arm/disarm in accordance with the button's user's global arming settings. Enter 0 if the button is not to be used to global arm the system (however, home partition arming will still occur). 1*58 Enter 1 to allow the RF Button user to force bypass all faulted zones. When attempting to arm the system, the keypad will beep once after pressing the button, if any faulted zones are present.
PROGRAMMING PARTITION-SPECIFIC DATA FIELDS General Procedure Values for some programming fields are system wide (global), and some can be different for each partition (partition-specific). If the system is set up for 2 partitions (field 2*00 = 2), the partition-specific programming fields are automatically skipped when programming the global fields. The table below lists the partitionspecific fields that can be defined for each partition. To access partition-specific fields, 1.
Partition-Specific Field Descriptions (continued) *29 Quick Arm Enter 1 to enable arming of the burglary system in AWAY, STAY, INSTANT or MAXIMUM modes by using the # key instead of the security code. When armed, reports closing as User 0 if open/close reporting for User #2 (typically a master level user) was enabled for a given partition. If quick arm is used, the installer code and authority level 5 code cannot disarm the system. Enter 0 if Quick Arm is not desired.
Section 4. PROGRAMMING WITH #93 MENU MODE General Information NOTE: The following fields should be preset before beginning: 2*00 (Number of Partitions); 1*32 (receiver type). In addition, receivers should be programmed via Device programming.
Zone Programming Important!: Note that before programming zone characteristics, field 2*00 (number of partitions) and field 1*32 (receiver type) must be programmed. This identifies the use of RF Receivers and the number of partitions being used in the system. Enter Programming mode, then press #93 to display "ZONE PROG?". Press 1 to enter ZONE PROGRAMMING mode. The ZONE PROG? following screens will appear. Press [*] to display the 1=YES 0=NO next screen. Press # to display a previous screen.
Zone Programming (continued) 20 INPUT TYPE RF TRANS. RF: Note that input types 4 & 5 are valid for certain 5800 series transmitters only (ex. 5801, 5802, 5802CP). When using 5700 series transmitters, always set the input type to type 3. The zone number of the transmitter identifies whether or not supervision is required (ex. 5700 wireless zone number 63 is not supervised).
Serial Number Enrolling/Deleting SERIAL # PROG? 0=NO 1=YES To enroll or delete a device's serial number, enter 1 (yes). Enter 0 to move to the Alpha Programming menu. ENTER ZONE NO. 00=QUIT Enter the zone number of the device to be enrolled or deleted. Press [*] to move to the next prompt. Enter 00 to quit Serial Number programming. If the device for that zone number was not programmed as a serial number input device in the Zone Programming menus, a prompt indicating such will appear.
Alpha Programming Entering Zone Descriptors If using an alpha keypad in the system, a user friendly English language description/location of all protection zones, partitions' keypad panics, polling loop short and RF receiver supervision faults can be programmed into the system. Each description can be composed of a combination of words (up to a maximum of 3) that are selected from a vocabulary of 244 words stored in memory, and any word can have an "s" or " 's " added to it.
Entering Zone Descriptors (continued) Adding Custom Words Ð 60 Ð 5. When all desired words have been entered, press key [8] to store the description in memory. 6. To review the zone descriptions, key [#] plus zone number (e.g., #01). To edit zone descriptions, key [*] plus zone number (e.g., *01) 7. To exit the zone description mode, key 00. N O T E : Alpha descriptor entry can be entered locally at the alpha keypad or remotely using AdemcoÕs V-Link¨ downloading software (Rev.
Creating Partition Descriptors Creating A Custom Message Display (Installer's Message) 1. Select "Part DESCRIPT." mode. The system will ask for the partition number desired. Enter the number as a single key. 2. Follow the same procedure as for CUSTOM WORDS, except that partition descriptors are limited to four (4) characters (ex. WHSE for warehouse). Normally, when the system is in the disarmed state, the following display is present on the Keypad.
ALPHA VOCABULARY (For Entering Alpha Descriptors. To select a word, press [#] followed by the word's 3-digit number.) Bulleted words in bold face type are those that are also available for use by the 4285 phone module. If using a phone module, and words other than these are selected for alpha descriptors, the phone module will not provide annunciation of those words. NOTE: This vocabulary is not to be used for relay voice descriptors.
Device Programming This menu is used to program keypads, receivers and relay modules. From Data Field Programming mode, press #93 to display "ZONE PROG?". Press 0 repeatedly to display "DEVICE PROG?". DEVICE PROG? 1=YES 0=NO Press 1 to enter DEVICE PROGRAMMING mode. DEVICE ADDRESS 01-15, 00 = QUIT Enter the 2-digit device number as set by the device's DIP switches (01-15). Press [*] to accept entry. Enter 00 to return to the main menu. See NOTE below.
VIM Voice Interface Module Prompts If device type 7 (VIM) is selected, the following prompts will appear. VIM PARTITION? NOTE: The VIM reports supervisory faults as zone 93. Make sure to program a response type (trouble = response type 05) and report code to zone 93 using #93 Menu Mode - ZONE PROGRAMMING. MAX 2WAY T.O.
This is recommended if dual reporting is selected, to allow the report to be sent to primary and secondary numbers. The display returns to the DEVICE ADDRESS prompt for entry of the next device or exit from DEVICE PROGRAMMING mode. Relay Programming These relay output actions are performed in response to a programmed condition. The VISTA-40 supports up to eight (8) X-10 and/or relay outputs. The X-10 interface is made via a 4300 plug-in transformer.
The following is a list of choices for (ZT): CHOICES FOR ZONE TYPES: 00 = No Response (Not Used) 01 = Entry/Exit #1 02 = Entry/exit #2 03 = Perimeter 04 = Interior Follower 05 = Trouble Day/Alarm Night 06 = 24 Hr Silent 07 = 24 Hr Audible 08 = 24 Hr Aux 09 = Fire Alarm or Trouble 10 = Interior w/Delay 23 = No alarm response CHOICES FOR SYSTEM OPERATION: 20 = Arming-Stay (5800 RF) 21 = Arming-Away (5800 RF) 22 = Disarming (Code+Off) (5800 RF) 31 = End of Exit Time 32 = Start of Entry Time 33 = Any Burglary
NOTE: 4204 Relay Module must be rev. "V3" or higher to activate temporal pulsing. 02 ÊÊA EV ZL ZT P STT Ê 0Ê 0 0 00 The keypad will display a summary START screen. 02 ÊÊA EV ZL ZT P STOP 0 0 0 00 The keypad displays a summary STOP screen. 02 RELAY ACTION NO RESPONSE Enter the desired relay action as follows: 0=not used; 1=closed for 2 secs.; 2=stay closed; 3=pulse on/off (temporal pulse). Note: The 4204 relay must have ÒV3Ó later installed to activate temporal pulse.
Zone List Programming After entering all relay menu items, up to four (4) zone lists can be entered by entering 00 at the ENTERÊRELAYÊNo. prompt. Enter Zone LIST 00=QUIT 00 Enter the zone list number 1-4. 01 Enter Zn Num. 00=QUIT 00 Enter each zone to be included in this zone list, pressing [*] to enter each zone number. 01 Del Zn LIST? Enter 0 to save the zone list entered. Enter 1 to delete that zone list. 01 Delete Zone? 0=NO 1=YES Enter 1 to delete one or more zones in that zone list.
Programming The Vim For Relay Triggering On Supervision Fault To program the system to trigger a relay upon an VIM fault, use the Relay Programming Menu (as described earlier) but enter the following values at the appropriate prompts. When programmed, the relay activates upon VIM failure and deactivates when the operation of the VIM is restored. 0 2 START EVENT TROUBLE 3 Enter 3 (trouble) as the event code to start the relay action. 0 2 START: ZN TYPE Enter the start zone type code 64 (VIM Fail).
Relay Voice Descriptors and Custom Word Substitutes Vocabulary Word Index Air....................116 Alarm ...............255 And .................067 Apartment........117 Appliances .......161 Area.................118 Attic.................119 Baby................120 Back ................121 Bar...................122 Basement ........021 Bathroom .........051 Battery .............053 Bed .................092 Bedroom..........015 Blower .............123 Boiler...............124 Bright...............
Section 5. SYSTEM COMMUNICATION COMMUNICATION FORMATS Split/Dual Reporting Dual reporting (*51) sends all reports to both primary and secondary phone numbers. Split reporting allows reports to be divided between the phone numbers according to the field's (1*34) selections. Split/Dual reporting can be selected by enabling dual reporting and enabling one of the split reporting options in field 1*34.
In 4+2 reporting a unique 2-digit code for each zone is reported. A 4-digit account number followed by a 2-digit code is sent, where the first digit is the actual event, such as in ALARM, RESTORE, or TROUBLE, etc., and the second digit of the code represents the "zone" where the event occurred. (but not necessarily the actual zone number). Each code in itself is unique to a specific zone. If desired, the actual zone number can be reported by entering the corresponding 2-digit zone number (ex.
Contact ID Reporting This is the only format that can identify all 64 protection zones by their unique zone (Contact) ID numbers, and provides a 1-digit event qualifier and 3-digit, specifically defined event code which quickly identifies the condition being reported. Contact ID reports in DTMF (Dual Tone Multi-Frequency @ 10 characters per second) and responds to a 1400 Hz followed by 2300 Hz handshake, and a 1400 Hz kissoff. This format also uses checksum instead of two message verification.
COMMUNICATION PROGRAMMING General Information To help expedite the installation, the system provides 4 different communication defaults (Low Speed, Ademco Express, Ademco High Speed & Ademco's new Contact ID). These defaults automatically program industry-standard code assignments for zones, keypad panics, non-alarm and supervisory conditions, and can be loaded at any time without affecting non-communication program fields.
COMMUNICATION PROGRAMMING GUIDE Field # *46, *48 *52, *53 *79, *80 *49 *81, *82 *54, *56, *59, *61, *64, *66, *69, *71, *74, *76 *55, *57, *60 *62, *65, *67, *70, *72, *75, *77 *58, *63, *68, *73, *78 event *50 NOTES Low Speed Choose transmission speed and frequency Send as either 4+2 or expanded Enables alarm restores Add checksum digit Define codes and selects 4+1 or 4+2 Defines alarm event code Contact ID No effect High Speed No effect Express No effect No effect No effect No effect Enables alar
¥ Disables reporting Troubles, Trouble Restores, Bypass, Bypass Restores for all zones.
COMMUNICATION DEFAULTS for LOW SPEED FORMAT (*94 then *80) *45 PRIMARY FORMAT 0Ê Ademco Low Speed *51 DUAL REPORTING * 46 LOW SPEED FORMAT (Primary) 0Ê Ademco Low Speed *52 STANDARD/EXPANDED REPORT FOR PRIMARY *47 SECONDARY FORMAT 0Ê Ademco Low Speed *48 LOW SPEED FORMAT (Sec.
COMMUNICATION DEFAULTS for ADEMCO EXPRESS FORMAT (*94 then *81) *45 PRIMARY FORMAT 3Ê * 46 LOW SPEED FORMAT (Primary) 0Ê *47 SECONDARY FORMAT 3Ê *48 LOW SPEED FORMAT (Sec.
ARM STAY & TIME SET REPORT CODES 1*4 0 1*4 1 First Digit Second Digit Armed STAY Ê0|0Ê Ê0|0Ê Time/Date set or event log reset Ê0|0Ê Ê0|0Ê
COMMUNICATION DEFAULTS for ADEMCO HIGH SPEED FORMAT (*94 then *82) *45 PRIMARY FORMAT 2Ê * 46 LOW SPEED FORMAT (Primary) 0Ê *47 SECONDARY FORMAT 2Ê *48 LOW SPEED FORMAT (Sec.
ARM STAY & TIME SET REPORT CODES 1*4 0 1*4 1 First Digit Second Digit Armed STAY Ê0|0Ê Ê0|0Ê Time/Date set or event log reset Ê0|0Ê Ê0|0Ê
COMMUNICATION DEFAULTS for ADEMCO's CONTACT ID FORMAT (*94 then *83) *45 PRIMARY FORMAT 1Ê * 46 LOW SPEED FORMAT (Primary) 0Ê *47 SECONDARY FORMAT 1Ê *48 LOW SPEED FORMAT (Sec.
ARM STAY & TIME SET REPORT CODES 1*4 0 1*4 1 First Digit Second Digit Armed STAY Ê0|0Ê Ê0|0Ê Time/Date set or event log reset Ê0|0Ê Ê0|0Ê Ð 83 Ð
Section 6. DOWNLOADING REMOTE DOWNLOADING What Is Downloading? How Does Downloading Work? Advisories: 1. Alarm and trouble responses and reports are disabled during on-line time. Should an event occur during this time, the response will take place and the report will go through as soon as the remote access sequence is completed. Alarm and trouble conditions are not ignored, they are simply delayed. 2. The keypads are inactive during downloading communication, and resume normal functions after hang up.
What Can Be Done Once Panel Is "On-Line"? ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ How Secure Is Downloading? NOTES: Arm the System in the Away Mode; Disarm the System Bypass a Zone Force the System to Accept a New Program Download Shut Down Communication (dialer) Functions (non-payment of monitoring fees in an owned system) Shut Down all Security System Functions (non-payment for a leased system) Inhibit Local Keypad Programming (prevents takeover of your accounts) Leave a message for customer (alpha keypads ONLY) Command
DIRECT WIRE DOWNLOADING Direct Wire Downloading Connections The VISTA-40 can be downloaded without using a modem or telephone line by using AdemcoÕs V-Link¨ downloading software (Rev. 4 or higher) or AdemcoÕs Compass Windows downloading software, and a 4100SM Serial Module. The direct wire downloading connection is to be temporary, and is not part of the permanent installation. Direct wire downloading is meant as a tool for the installer during the installation process.
Section 7. SETTING THE REAL-TIME CLOCK PROCEDURE IMPORTANT: This method is different from the previous method of setting the clock. NOTE: A 6139 alpha keypad must be used to set the real-time clock, or the clock can be set via the Downloader software. Only users with installer or master authority level can set the real-time clock. To enter real-time clock mode, enter installer or master code + #63.
PART 3 SYSTEM OPERATION & TESTING Ð 88 Ð
Section 1. SYSTEM OPERATION SECURITY ACCESS CODES General Information The System allows up to a total of 70 security access codes to be assigned (maximum of 69 in a given partition), each identified by a user ID number. In addition, the Quick Arm feature can also be programmed, which enables the [#] key to be pressed instead of entering the security code when arming the system. The code must still be entered when disarming the system.
User Codes & Levels Of Authority (cont.) Open/Close Reporting Note: When adding a user, the system will only prompt for Open/Close report capability if the user is being added by the Installer. When a Master or Manager adds a new user, the new user's Open/Close reporting enable will be the same as that of the Master or Manager adding the user.
¥ A user can only be DELETED or CHANGED from within the partition he is assigned. ¥ User numbers must be entered as 2-digit entries. Single digit user numbers must, therefore, always be preceded by a "0" (example, 03, 04, 05, etc.). Make sure the end user understands this requirement. Temporary codes are entered as 4-digit numbers. Important!: Unless Ademco Contact ID reporting is used, only user codes #1Ð#15 can uniquely report to the central station using the communication formats provided.
To ADD a Master, Manager or Operator code Installer must program at least one Master code. Or Master or Manager code, but must be code with higher level of authority than the code being changed. (i.e. Master code can add a Manager or Operator level code, but cannot add another Master code; a Manager code can add an Operator level code, but cannot add a Master or another Manager code). Ð 92 Ð Important!: During user code entry, normal key depressions at other keypads in a partition will be ignored.
Part. 2 Ð SHOP ? 0 = NO , 1 = YES Part. 1 S WHSE User 03 Auth=3G. To CHANGE a Master, Manager or Operator code Press 0 (NO) or 1 (YES), depending on whether or not this user will have access to the displayed partition number. If NO, the keypad displays this prompt for the next partition number in sequence. If YES, the keypad prompts for the following: ¥ UserÕs authority level in the displayed partition (see Authority Level prompt above).
KEYPAD FUNCTIONS General Information Phone Module Arming Functions Note that if QUICK ARM is enabled (field *29), the [#] key can be pressed instead of entering the security code, for any of the arming procedures (Away, Stay, Instant, Maximum, etc.). The keypad allows the user to arm and disarm the system, and perform other system functions, such as bypassing zones, view messages from the central station and display zone descriptors.
Bypassing Zones Enter code + BYPASS [6] + zone number. To automatically bypass all faulted zones, use "Quick Bypass" method: Enter code + BYPASS + [#]. Chime Mode Enter code + CHIME [9]. To turn chime mode off, enter code + CHIME again.
Panic Keys There are three panic keys (or panic key pairs) that, if programmed, can be used to manually initiate alarms and send a report to the central station. Each key pair can be individually programmed for 24-Hour Silent, Audible or Auxiliary (Emergency) responses. The panic function is activated when the appropriate key is pressed (or key pair is pressed at the same time).
¥ "LO BAT" (alpha) or "BAT" (fixed-word) and a zone descriptor, and a once per minute beep at the Keypad indicates that a low battery condition exists in the wireless transmitter displayed. Silence the warning sound by pressing any key. "SYSTEM LO BAT" (alpha) or "BAT" with no zone number (fixed-word) indicates a low battery condition with the system's backup battery.
Note: If the operator makes a mistake in entering the proper 4-digit ID code, the operator just needs to re-enter the correct code. If after 5 minutes have elapsed without the central station callback, only a new alarm will initiate a new 2-way voice session. Operator Commands The following table summarizes the central station operator commands available. To perform a command, the operator simply presses the appropriate telephone key(s).
The system allows viewing of any partition's event log. Enter the partition number for the partition whose events are to be displayed. Entering 0 (NO) will display all events that occurred in the system regardless of partition. For display purposes, events are stored on a partition by partition basis (except system events), and are grouped into five categories as follows.
Section 2. TESTING THE SYSTEM Using The Test Mode After the installation is completed, the Security System should be thoroughly tested on a partition by partition basis as follows: 1. With the System in the disarmed state, check that all zones are intact. If DISARMED - Press [*] to show faults is displayed, press the [*] key to display the descriptors of the faulted zone(s).
2-Way Voice Test Mode At the Protected Premises: To test the VIM and 6139AV keypad 2-way voice operation, both the installer at the protected premises and the central station operator do the following. NOTE: The VIM has built-in LEDs which identify its operating mode. It can be helpful to view these LEDs when performing the following test. To view the LEDs, remove the VIM's cover and refer to the table that follows.
Turning The System Over To The User 1. Fully explain the operation of the system to the user by going over each of its functions as well as the User's Manual supplied. 2. In particular, explain the operation of each zone (entry/exit, perimeter, interior, fire, etc.). Be sure the user understands how to operate any emergency feature(s) programmed into the system.
Section 3.
Wireless System House Id Sniffer Mode = Code + [#] + [2] (installer only) Transmitter ID Test = Code + [#] + [3] (installer only) Go/No Go Test = Code + TEST [5] Key) Keypad Functions Arming Away: Arming Stay: Arming Instant: Arming Maximum: Quick Arm: Global Arming: Disarming: Bypassing Zones: Quick Bypass: Chime Mode: Enter Code + Away [2]. Enter Code + Stay [3]. Enter Code + Instant [7]. Enter Code + Maximum [4]. Use # Key Instead Of User Code Followed By Any Of The Above Arming Mode Keys.
Section 4. REGULATORY AGENCY STATEMENTS UL INSTALLATION REQUIREMENTS The following requirements apply to UL Residential Burglary installations: 1. All partitions must be owned and managed by the same person(s). 2. All partitions must be part of one building at one street address. 3. The audible alarm device(s) must be placed where it/they can be heard by all partitions. 4. The Control cabinet must be protected from unauthorized access.
CANADIAN DEPARTMENT OF COMMUNICATIONS (DOC) STATEMENT NOTICE The Canadian Department of Communications label identifies certified equipment. This certification means that the equipment meets certain telecommunications network protective, operational and safety requirements. The Department does not guarantee the equipment will operate to the user's satisfaction.
DIP SWITCH TABLES FOR ADDRESSABLE POLLING LOOPLOOP DEVICES DIP SWITCH TABLES FOR ADDRESSABLE POLLING DEVICES 4208 ZONE EXPANDER 4190WH ZONE EXPANDER 4192D/4192SDT/4192CP SMOKE DETECTORS DIP + DIP DIP SIDE VIEW (UP) SHOWN SET FOR ID 10 (A) SIDE VIEW (UP) 1 2 3 4 5 UP APPLIES TO TABLE A & B UPLY SHOWN SET FOR ID 10 (A) APPLIES TO TABLE A UPLY SHOWN SET FOR ID 10 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 SIDE VIEW (DN) DN DN POS.1: LOOPS 1 & 2 RESPONSE TIME: FAST W/TABLE UP A DN B SLOW DN UP POS.
DIP DIPSWITCH SWITCHTABLES TABLESFOR FORPOLLING POLLINGLOOP LOOPDEVICES DEVICES MIRROR SHOWN SET FOR ID 10 (A) 1 2 3 4 5 6 7 1 2 3 4 5 6 DN DN — } } UP A DIP SWITCH POSITION 1 2 3 4 5 — — — — — — UP UP UP UP UP UP UP UP UP UP UP UP UP UP UP UP UP UP UP UP UP UP — — — — — — — — UP UP UP UP UP UP UP UP — — UP UP UP UP — — — — UP UP UP UP — — — — UP UP UP UP UP UP — — UP UP — — UP UP — — UP UP — — UP UP — — UP UP — UP — UP — UP — UP — UP — UP — UP — UP — UP — UP — UP THIS TABLE FOR DIPS
DIPDIP SWITCH TABLES SYSTEM WIRELESS DEVICES SWITCH TABLESFOR FOR5700 5700RF SERIES WIRELESS DEVICES HOUSE ID SWITCH SETTING FOR ALL DEVICES EXCEPT 5716 2 3 4 5 UP UP UP UP UP UP UP UP UP UP UP UP UP UP UP — — — — — — — — — — — — — — — — UP UP UP UP UP UP UP — — — — — — — — UP UP UP UP UP UP UP UP — — — — — — — — UP UP UP — — — — UP UP UP UP — — — — UP UP UP UP — — — — UP UP UP UP — — — — UP — — UP UP — — UP UP — — UP UP — — UP UP — — UP UP — — UP UP — — UP UP — — — UP — UP — UP — UP — UP — UP — UP
Section 5. SPECIFICATIONS VISTA-40 CONTROL Physical: 12-1/2"W X 14-1/2"H X 3"D Electrical: VOLTAGE INPUT: Ademco No. 1361 Plug-In Transformer (use 1361CN in Canada) or 4300 transformer (for X-10 installations) rated 16.5VAC, 40 VA. ALARM SOUNDER OUTPUT: 10VDC-13.8VDC, 2.8 amps max., 750mA less aux. current draw (UL1023/UL985 installations). AUXILIARY POWER OUTPUT: 9.6VDC-13.8VDC, 750mA max.
CONTACTING TECHNICAL SUPPORT PLEASE, Before you call Technical Support, be sure you: ¥ READ THE INSTRUCTIONS! ¥ Check all wiring connections. ¥ Determine that the power supply and/or backup battery are supplying proper voltages. ¥ Verify your programming information where applicable. ¥ Note the proper model number of this product, and the version level (if known) along with any documentation that came with the product. ¥ Note your ADEMCO customer number and/or company name.
WARNING! THE LIMITATIONS OF THIS ALARM SYSTEM While this System is an advanced wireless security system, it does not offer guaranteed protection against burglary, fire or other emergency. Any alarm system, whether commercial or residential, is subject to compromise or failure to warn for a variety of reasons. For example: ¥ Intruders may gain access through unprotected openings or have the technical sophistication to bypass an alarm sensor or disconnect an alarm warning device. ¥ Intrusion detectors (e.g.
WEEKLY TESTING IS REQUIRED TO ENSURE PROPER OPERATION OF THIS SYSTEM. THIS DEVICE COMPLIES WITH PART 15 OF FCC RULES. OPERATION IS SUBJECT TO THE FOLLOWING TWO CONDITIONS: (1) IT MAY NOT CAUSE HARMFUL INTERFERENCE. (2) IT MUST ACCEPT ANY INTERFERENCE THAT MAY CAUSE UNDESIRED OPERATION. RED (+) 2. Zone 1 supports 2-wire smoke detectors. See Installation Instructions for recommended type and maximum number of detectors supported. Zone 7 may be used for remote keyswitch arming/disarming. 3.
ADEMCO LIMITED WARRANTY Alarm Device Manufacturing Company, a Division of Pittway Corporation, and its divisions, subsidiaries and affiliates ("Seller"), 165 Eileen Way, Syosset, New York 11791, warrants its products to be in conformance with its own plans and specifications and to be free from defects in materials and workmanship under normal use and service for 18 months from the date stamp control on the product or, for products not having an Ademco date stamp, for 12 months from date of original purchas
N5944-6ZZ ADDENDUM TO: 6/97 VISTA-40 and VISTA 50P/UL Installation Instructions NEW "QED" DEVICE ENROLLMENT PROCEDURE FOR 5800 SERIES TRANSMITTERS AND SERIAL NUMBER POLLING LOOP DEVICES This addendum describes the new procedure for "enrolling" 5800 series transmitters or serial number polling-loop devices into the system.
E NTE R ZN NO . 0 0 = Q UIT 10 4. Enter the zone number that you wish to program. As an example, zone 10 is shown here. Press [✱] to continue. Zone 10 entered ↑ 1 0 ZT P RC IN: L 00 – –– ––: – 5. A display will appear, showing a summary of that zone's programming. If the zone is not programmed, the display will appear as shown here. If checking a zone's programming, and it is programmed satisfactorily, press [#] to back up one step and enter another zone number, if desired.
10 LOOP # 1 10 LEARN S/N? 1 = YES, 0 = NO 1 10 INPUT S/N Axxx-xxxx 10. The cursor should now be flashing on the loop number. The default is "1." To accept this, press [✱]. If a different loop number is being used on this device, enter the loop number (1-4) and press [✱] to continue (see the loop designations for various RF transmitters on page 8 of this addendum). The loop number must be entered here, whether using Zone Programming or Sequential Mode to "enroll" serial numbers.
At any time during this step, you may press the [✱] key on the keypad or the upper left-hand button of the program tool if you are satisfied with the serial and loop number combination that has been enrolled, regardless of whether or not the enrolled input has been "confirmed." If the incorrect device has been enrolled, press the # key on the keypad or upper right-hand button on the program tool to delete the serial number and return to the "LEARN S/N" prompt.
00 PROG AS BR:3 A123-4567 3 In this example, the serial number is A123-4567. Once enrolled, the upper left-hand button of the program tool can be pressed to ready the system for enrolling a transmitter into the system. The serial number for the program tool will only remain in the system until the programming mode is exited. (Entering ✱ 97 will not delete the tool.) Press [✱] to continue. Pressing the # key on the keypad will cause the system to back up to the "PROGRAM TOOL ?" prompt.
If you do not wish to enroll the zone displayed, press the # key on the keypad or the upper right-hand button on the program tool (a long beep will be heard to verify). The following prompt will appear: 10 LEARN S/N? 0 = NO, 1 = YES 0 To enroll now, enter "1" (YES). If "0" (NO) is entered, the following prompt will appear : E NTE R ZN NUM. (0 0 = Q UIT) 1 2 Zone Number Entered ↑ Enter the next zone number to be enrolled (e.g., zone 12).
8. The system will search for the next zone that does not have a serial number associated with it. If one is found, the prompt in step 5, along with the appropriate zone number, will be displayed. Follow steps 5 and 6 for the remaining zones. After all zones have been displayed, whether enrolled or not, the "ENTER ZN NO." prompt will appear. Enter "00" to exit the Sequential mode and return to data field programming mode. When you have finished programming all zones, test each using the system's TEST mode.
5800 Series Transmitter Input Loop Identification • All of the transmitters illustrated below have one or more unique factory assigned input (loop) ID codes. Each of the inputs requires its own programming zone (e.g., a 5803's three inputs require three programming zones). • Transmitter inputs entered as: "RF" (Supervised RF) Type send periodic check-in signals, as well as fault, restore and low battery signals. The transmitter must remain within the receiver's range.