- Guardian Liquid Cooled Gas Engine Generator Specifications
  COMMERCIAL 80 kW 
KW RATING  80
ENGINE SIZE  4.6 Liter V-8
GENERATOR OUTPUT VOLTAGE/KW - 60Hz  KW  AMP  CB Size
  120/240V, single phase, 1.0 pf  80 LP / 78 NG  333.3 LP / 325 NG  400
  120/208V, 3-phase, 0.8 pf  80 LP / 78 NG  277.9 LP / 270.9 NG  300
  120/240V, 3-phase, 0.8 pf  80 LP / 78 NG  240.8 LP / 234.8 NG  300
  277/480V, 3-phase, 0.8 pf  80 LP / 78 NG  120.4 LP / 117.4 NG  150
GENERATOR LOCKED ROTOR KVA
 AVAILABLE @ VOLTAGE DIP OF 35%
  Single phase or 208V & 240V 3-phase    160
 480V 3-phase    185
ENGINE FUEL CONSUMPTION 
(Natural Gas) (Propane)    Natural Gas  Propane 
     (ft
3
/hr.) (gal/hr.) cu ft/hr
 Exercise cycle    131  1.45  53 
  25% of rated load    312  3.45  126
  50% of rated load    600  6.64  241   
  75% of rated load    835  9.25  336
  100% of rated load    1154  12.78  465
ENGINE COOLING
 Air flow 
(inlet air including alternator and combustion air) ft
3
/min. 5,300
  System coolant capacity  US gal.   4.0
  Heat rejection to coolant   BTU/hr.  316,000
  Max. operating air temp. on radiator  °C (°F)  60 (150)
  Max. ambient temperature  °C (°F)  50 (140)
COMBUSTION AIR REQUIREMENTS
  Flow at rated power 60 Hz  cfm  250
SOUND EMISSIONS IN DBA
  db(A) @ 23 feet in exercise mode    64 
  db(A) @ 23 feet at normal operating load    74 
EXHAUST
  Exhaust flow at rated output 60 Hz  m
3
/min. (cfm)  720 
  Exhaust temp. at muffler outlet  °F  840 
ENGINE PARAMETERS
  Rated synchronous RPM  60 Hz  3600
  HP at rated KW  60 Hz  130
POWER ADJUSTMENT FOR AMBIENT CONDITIONS
 Temperature Deration
    3% for every 10 °C above - °C  25 
    1.65% for every 10 °F above - °F  77
 Altitude Deration 
    1% for every 100 m above - m  183   
    3% for every 1000 ft. above - ft.  600
OPERATING DATA
COMMERCIAL 80 kW
RATING: All three phases units are rated at 0.8 power factor. All single phase units are rated at 1.0 power factor. STANDBY RATING: Standby ratings apply to installations served by a reliable utility 
source. The standby rating is applicable to varying loads for the duration of a power outage. There is no overload capability for this rating. Ratings are in accordance with ISO-3046-1. Design and 
specifications are subject to change without notice. Maximum wattage and current are subject to and limited by such factors as fuel Btu content, ambient temperature, altitude, engine power 
and condition, etc.
COMMERCIAL SERIES