User Guide
16
EDGE 6
EDGE 5
EDGE 4
EDGE 3
EDGE 2
EDGE 1
COM
COM
+
–
DUAL
GATE
INTER-
FACE
RX
TX
G
R
B
GTO
RCVR.
CLOSE
OPEN
FIRE DEPT.
SHAD. LOOP
SAFE LOOP
ENTRY LOOP
FREE EXIT
CYCLE
COMMON
COMMON
COMMON
COMMON
LOCK 1
LOCK 2
ALARM
AUX 2
ACCES. PWR
24VDC
–
+
–
+
TB11
TB9
TB10
TB8
TB7
TB6
TB5
TB4
TB3
TB2
TB1
Terminals
SENSOR ERR.: Indicates obstruction sensing circuitry has malfunctioned.
LIM SW ERR.: Indicates a fault in the limit switch or limit switch wiring (This LED cannot be reset with the RST
/ LEARN button).
OPEN MTR.: Control board does not detect the operator motor.
INTERN ERR.: Indicates a microprocessor error has occurred. An internal error
cannot be reset by pressing the LEARN/RESET button. The ON/OFF switch must be turned OFF, then back ON to
reset the LED.
Error Condition LEDs (Press RST / LEARN to clear these LEDs)
Terminals (Note: use common connections for ground. To
ground CLOSE/OPEN, FIRE DEPT., SHAD. LOOP, ENTRY
ENAB, ENTRY LOOP, FREE EXIT, and CYCLE, use the center
post).
EDGE 1 – EDGE 6 : These six terminals accommodate safety
edges and photo beams.
COM (common): Terminal for connecting a ground wire.
DUAL GATE INTERFACE RX TX: This terminal allows the
addition of a second gate operator for dual gate systems. ONLY
Belden Wire
®
(see Installing a Dual Slide Gate System on pages 22-
23) is compatible with this terminal. All four (4) connectors plus one
(1) COMMON must be wired.
GTO RCVR.: For connecting a GTO receiver ONLY. Other receivers
may be connected to the 24VDC terminal block (see CAUTION at
24VDC).
CLOSE/OPEN: OPEN requires constant pressure on entry device to
pen the gate; CLOSE requires constant pressure on entry device to
close the gate. NOTE: When a constant pressure entry device is
installed the unit will not accept any other open or close input except
FIRE DEPT and FREE EXIT (requires constant input).
FIRE DEPT.: N/O contact reserved for public safety agency use
(e.g., fire box) only.
SHAD. LOOP: Shadow loop connection for swing gates.
SAFE LOOP: N/O contact that prevents the gate from closing if the
safety device (ground loop, photo beam, etc.) is activated.
ENTRY LOOP: N/O contact for entry device.
FREE EXIT: N/O contact for an exit loop or exit wand.
CYCLE: N/O contact for doorbell button or key switch.
COMMON (ground): Terminal for connecting a ground wire
24 VDC: Accommodates accessory power up to
1
/2 A. This is a fused
power supply (
1
/2 A; 3AG fuse only). CAUTION: Accessories other
than 24 Vdc or rated higher than
1
/2 A require a separate power supply
(not provided).
AUX2: Activates devices such as another unit in a 2-stage security
application.
ALARM: Activates devices such as lights or alarms when gate is
obstructed.
LOCK2: Provides a contact closure when the gate is in motion.
LOCK1: Provides a contact closure when the gate is not in motion.