Installation and Operating Instructions
Table Of Contents
- English (GB)
- 1. General information
- 2. Installing the product
- 3. Starting up the product
- 4. Product introduction
- 5. Control functions
- 6. Setting the product
- 6.1 Setting the sensor type
- 6.2 Setting the start level
- 6.3 Setting the stop level
- 6.4 Setting the high level
- 6.5 Stop delay
- 6.6 Power-on delay
- 6.7 Dry-running protection
- 6.8 Using the same level switch for the start and stop level
- 6.9 "Multipump settings"
- 6.10 "Antiseizing"
- 6.11 Signal detection time
- 6.12 Setting the maximum number of restarts with Grundfos GO Remote
- 6.13 Setting the service interval with Grundfos GO Remote
- 6.14 Operating the product
- 6.15 Motor protection
- 6.16 Alarm reset
- 6.17 Setting the buzzer with Grundfos GO Remote
- 6.18 Setting units for Grundfos GO Remote
- 6.19 Setting units for the operating panel with Grundfos GO Remote
- 6.20 GENIbus
- 6.21 Security
- 6.22 Starting the startup wizard with the operating panel
- 7. Servicing the product
- 8. Fault finding the product
- 8.1 Overview of alarm and warning codes
- 8.2 Code 2 (Power phase missing)
- 8.3 Code 4 (Too many motor restarts)
- 8.4 Code 9 (Power phase sequence wrong)
- 8.5 Code 12 (Service needed)
- 8.6 Code 22 (Moisture in motor of pump)
- 8.7 Code 25 (Wrong configuration)
- 8.8 Code 26 (Contactor shorted)
- 8.9 Code 48 (Motor is overloaded)
- 8.10 Code 51 (Blocked)
- 8.11 Code 57 (Missing water in the application)
- 8.12 Code 69 (Winding temperature too high)
- 8.13 Code 72 (Internal fault)
- 8.14 Code 76 (Internal fault)
- 8.15 Code 84 (Memory storage media faulty)
- 8.16 Code 85 (Internal fault)
- 8.17 Code 117 (Door opened)
- 8.18 Code 159 (Communication error CIMxxx)
- 8.19 Code 163 (Drive unit configuration fault)
- 8.20 Code 165 (Signal fault)
- 8.21 Code 191 (High water level)
- 8.22 Code 205 (Level switch inconsistency)
- 8.23 Code 220 (Contactor wear out)
- 8.24 Code 229 (Water on floor)
- 9. Technical data
- 10. Disposing of the product
Pump output terminal
Current: See nameplate.
IEC stranded 0.75 to 2.5 mm
2
.
IEC solid 1.0 to 4.0 mm
2
.
UL stranded or solid AWG 18 to 12.
Screw torque: 1.2 Nm.
Alarm relay terminals
277 VAC nominal and 24 VDC nominal.
Nominal current 10 mA to 2 A AC/DC.
Pilot duty.
UL: solid AWG 28 - 12, stranded AWG 30-12.
IEC: solid or stranded 0.2 - 2.5 mm
2
.
Stripping lenght: 7-8 mm.
Screw torque: 0.5 Nm.
Relay output 1 and 2
Minimum contact load: 10mA AC/DC.
Potential-free changeover contacts.
IEC: solid or stranded 0.2 - 2.5 mm
2
.
UL: solid AWG 28 - 12, stranded AWG 30-12.
Stripping lenght: 7-8 mm.
Screw torque: 0.5 Nm.
Digital input
IEC: solid or stranded 0.5 - 2.5 mm
2
, flexible 0.25 -
1.5 mm
2
.
UL: solid or stranded AWG 28-12.
Stripping length: 5-6 mm.
Digital input mode
Low logic level below 1.8
V.
High logic level higher
than 2.7 V.
Active can be HIGH or
LOW, set via Grundfos
GO Remote.
DIO terminals
Digital input mode
Low logic level below 1.8
V.
High logic level higher
than 2.7 V.
Active can be HIGH or
LOW, set via Grundfos
GO Remote.
Digital output mode
Open collector.
Current sink capability
75 mA, no sourcing.
Overcurrent protected.
Active can be HIGH or
LOW, set via Grundfos
GO Remote.
DIO terminals
Digital input mode
Low logic level below 1.8
V.
High logic level higher
than 2.7 V.
Active can be HIGH or
LOW, set via Grundfos
GO Remote.
Digital output mode
Open collector.
Current sink capability
75 mA, no sourcing.
Overcurrent protected.
Active can be HIGH or
LOW, set via Grundfos
GO Remote.
PTC
IEC: solid or stranded 0.2 - 2.5 mm
2
.
UL: solid AWG 28-12, stranded AWG 30-12.
Stripping length 7-8 mm.
Screw torque: 0.5 Nm.
Pt100 or Pt1000 inputs (Pt)
Use Pt100 for short wires.
Use Pt1000 for long wires.
Solid or stranded wire: AWG 28-12 or maximum 2.5
mm
2
.
IEC: solid or stranded 0.5 - 2.5 mm
2
, flexible 0.25 -
1.5 mm
2
.
UL: solid or stranded AWG 28-12.
Stripping length: 5-6 mm.
Power supplies, +24 V
Output voltage: 24 VDC - 10 % to + 10 %.
Maximum 250 mA on each terminal.
Weight
See nameplate.
Altitude
Maximum 2000 m.
Pollution degree
Category 3.
29
English (GB)