Installation and Operating Instructions

Table Of Contents
Pos. Symbol Description
12
Operating mode for the pump:
On: The pump has been
switched on manually.
Off: The pump has been
switched off manually.
Auto: The pump is
running automatically
based on settings.
13 Display
The display shows the pump
status.
14
Setpoint
5.00 bar
Operaring mode
Normal
Actual controlled value
4.90 bar
Control mode
Const. pressure
Status Settings Assist
1 2 3
56789
Lock symbol:
If the symbol is lit, the control
unit is locked from making
changes.
15
Alarm and warning symbol:
Red: Alarm
Yellow: Warning
The control unit enables manual setting and
monitoring of the system.
6. Setting the product
6.1 Setting the sensor type
6.1.1 Setting the sensor type with Grundfos GO
Remote
1. Go to Settings > Level control > Sensor type.
2. Select the type.
Analog sensors
Digital sensors
6.1.2 Setting the sensor type with the operating
panel
1. Press and hold OK until S-1 or S-2 starts
flashing.
2. Select the sensor type using the Up and Down
buttons.
S-1: Analog sensors
S-2: Digital sensors.
3. Press OK to confirm the setting.
4. Continuously press OK to confirm all other
settings and to exit the setup.
6.2 Setting the start level
6.2.1 Setting the start level with Grundfos GO
Remote
The settings apply to analog sensors. For digital
sensors, the setting is automatically activated.
1. Go to
Settings > Level Control > Start level
P1.
2. Set the start level for pump 1.
3. Go to Settings > Level control > Start level P2.
4. Set the start level for pump 2.
6.2.2 Setting the start level with the operating
panel
The settings apply to analog sensors. For digital
sensors, the setting is automatically activated.
1. Press and hold OK until the display and dry
running start flashing.
2. Continuously press OK until the indicator light for
the start level for pump 1 starts flashing.
TM071336
3. Set the start level for pump 1 by using
the Up and Down buttons.
4. Press OK.
The indicator light for the start level for pump 2
starts flashing.
TM071337
5. Set the start level for pump 2 by using
the Up and Down buttons.
6. Continuously press OK until the display stops
flashing.
The settings have now been stored.